background image

Figure 9. 

Enardo 2500 Series with an Elevated Pressure Setting

Pressure and Vacuum Setting Information

Both the Enardo 2000 and Enardo 2500 Series can reach 

various pressure settings in units of ounces or inches of 

water column. The minimum pressure setting that each 

3.  Replace the spring chamber and hood. Fasten 

them securely.

4.  Clear away any debris or buildup on the unit surface 

that may cause the vent to become lodged, impede air 

flow or add weight to the lid assembly (added weight will 

adjust the pressure setting of the vent).

Remote Monitoring Maintenance

1.  Maintain Smart Wireless Model Enardo 2000 EPRV’s in 

the same way as all standard EPRV’s.

2.  Take certain precautions when cleaning the transmitter. 

The surface resistivity of the antenna assembly is 

greater than 1 GΩ. To avoid electrostatic charge build-

up, it must not be rubbed or cleaned with solvents or 

dry cloth.

vent can achieve depends on the individual vent size and 

material. Minimum settings are reached when the unit is 

installed by itself. However, when weights are added to the 

arm of the unit, elevated pressures can be reached. These 

elevated settings are preset at the factory and should never 

be field adjusted.

Vacuum settings for the Enardo 2500 Series are set with a 

spring. For each setting that Fisher™ offers, there is a spring 

that is specifically designed to do the job. The standard 

settings available are 0.5, 0.75, 1 and 2 oz. Once again, 

these settings are preset at the factory and should never be 

field adjusted.

7

Enardo 2000 and Enardo 2500 Series

Outside North 

America Only

Summary of Contents for FISHIER Enardo 2000 Series

Page 1: ...n Either condition may result in equipment damage or personal injury Only a qualified person shall install or service the emergency pressure relief vent Figure 1 Enardo 2000 Series Emergency Pressure Relief Vent Figure 2 Enardo 2500 Series Emergency Pressure Relief Vent with Vacuum Figure 3 Enardo 2000 Series with Smart Wireless Monitoring Introduction Scope of the Manual This Instruction Manual p...

Page 2: ...um 304 Stainless steel and 316 Stainless steel Seal Buna N FEP Teflon and Viton Enardo 2500 Series Base Arm and Hood Carbon steel 304 Stainless steel and 316 Stainless steel Disk and Seal Support Aluminum and 316 Stainless steel Seal FEP Teflon Viton and Buna N Vacuum Spring 302 Stainless steel Vacuum Pallet and Vacuum Seat Polyphenylene Sulfide and 316 Stainless steel Certification EN IEC 60079 0...

Page 3: ...Number Product Identification and Marking Hazardous Locations Fisher Emergency Pressure Relief Vents are available with outer housings of carbon steel stainless steel or aluminum as indicated in Figure 4 Nameplate A nameplate is attached to the vent and contains the following information Model Number Ex 2024 24T 1 Connection Flange Size 24 in Serial Number Tag Number Optional Notified Body Number ...

Page 4: ... of the EPRV a proximity sensor and a wireless transmitter The built in proximity sensor detects the open or closed position using a magnetic target located on the arm assembly on the hinged end A signal is sent to the wireless transmitter which can then be sent to a control room via any WirelessHART Gateway This wireless sensor networking technology is based on the Highly Addressable Remote Trans...

Page 5: ...s Follow the instruction below for the installation of the Enardo 2000 and Enardo 2500 Series Install the Enardo 2000 and Enardo 2500 Series on the flange bolt patterns that match with bolt pattern of the vent The attachment flange base should be at level surface 1 Carefully remove the Enardo 2000 and Enardo 2500 Series from its crate The seal portion of the vents is delicate protect this surface ...

Page 6: ...nder pressure Follow the instruction below for the preventive maintenance of the Enardo 2000 and Enardo 2500 Series 1 Loosen fasteners on top of the vent and remove the hood and the spring chamber 2 Inspect and clear away any debris or buildup that may cause the vent to become lodged or impede air flow through the unit Do not adjust the height of the installed spring Clean the internal components ...

Page 7: ...ns when cleaning the transmitter The surface resistivity of the antenna assembly is greater than 1 GΩ To avoid electrostatic charge build up it must not be rubbed or cleaned with solvents or dry cloth vent can achieve depends on the individual vent size and material Minimum settings are reached when the unit is installed by itself However when weights are added to the arm of the unit elevated pres...

Page 8: ... 30 D103818X012 2015 2021 Emerson Process Management Regulator Technologies Inc All rights reserved 12 21 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for informa...

Reviews: