026-1400 Rev 3 22-MAR-2011

Facility Status Display (FSD)

Installation and Operation Manual

Summary of Contents for FSD

Page 1: ...026 1400 Rev 3 22 MAR 2011 Facility Status Display FSD Installation and Operation Manual ...

Page 2: ......

Page 3: ... omission in this manual even if advised of the possibility of such damages In the interest of continued product development Computer Process Controls Inc reserves the right to make improvements to this manual and the products described herein at any time without notice or obligation CE FCC COMPLIANCE NOTICE Class A compliance for Facility Status Display under Part 15 of the FCC Rules and CE EN 55...

Page 4: ......

Page 5: ... 4 1 Alarms Tab 11 5 4 1 1 Show RTN Alarms 11 5 4 1 2 Show Reset Advisories 12 5 4 1 3 Display Asset Alarm 12 5 4 1 4 Show Notices 12 5 4 1 5 Filter Advisories 12 5 4 1 6 Sort Data Points 12 5 4 1 7 Audible Alarm 12 5 4 1 8 Snooze Delay 13 5 4 1 9 Min Alarm Priority 13 5 4 2 Communications Tab 13 5 4 2 1 E2 IP Address 13 5 4 2 2 E2 IP Port 13 5 4 2 3 Display Number 13 5 4 3 General Tab 13 5 4 4 Ab...

Page 6: ...vi FSD Installation and Operation Manual 026 1400 Rev 3 22 MAR 2011 7 5 SOFTWARE SETUP 20 7 6 TROUBLESHOOTING 20 8 E2 ALARM ANNUNCIATOR SETUP 21 9 SOFTWARE UPDATES 21 10 SPECIFICATIONS 22 ...

Page 7: ...ost convenient for the user The FSD can be configured to filter out notices and or return to normal alarms and provides a quick review of all advisories and detailed advisory infor mation The FSD also receives alerts and provides an nunciated alarms and alarm information directly to store and department managers This compact unit can be installed virtually anywhere with a standard Ethernet connect...

Page 8: ...e 2 1 4 Step 4 Open the ferrite P N 090 0008 and run the Ethernet cable through wrapping the cable around the ferrite twice two turns near the Ethernet port LAN on the back of the display and close the ferrite Figure 2 2 around the Ethernet cable 5 Step 5 Plug the Ethernet cable into the RJ45 connector LAN on the back of the FSD s display module P N 750 5100 as indicated by Step 5 of Figure 2 3 6 ...

Page 9: ...he mounting sur face 8 0 high by 9 0 wide by at least 3 875 deep 20 32 cm high by 22 86 cm wide by at least 9 84 cm deep When cutting the mounting hole allow at least 1 2 1 27 cm clearance around the hole for face plate mounting Figure 2 5 2 Once this hole is cut mount the unit as desired Figure 2 4 and position the enclo sure so that the four support tabs are flush against the outside lip of the ...

Page 10: ...Leave 1 2 For Face Plate Mounting Open Side of Power Supply Box Mount Back Portion of FSD Power Supply Box Inside Wall 9 0 8 0 Support Tabs 4 3 875 Push out Tabs Conduit Knock outs Drawing Not To Scale Face Plate Screw Holes 4 Open Side of Power Supply Box 9 0 8 0 1 2 1 2 leave clearance each side for face plate 1 2 1 2 ...

Page 11: ...T tab cursor down to Status Display and then enter the desired number of devices Figure 3 2 3 2 STEP 2 Set Up IP Address for the FSD DHCP is enabled by default If you have a DHCP server the FSD will retrieve an IP Address automati cally If you wish to set up a static IP Address follow these steps 1 Touch the tool icon and enter the pass code on the security screen default code is 400 as shown in F...

Page 12: ...SD will communicate with must be en tered When the FSD is powered up for the first time the Start up or Boot Loader screens will appear 1 Log on by entering the passcode default code is 400 into the blank field on the first boot loader screen Figure 3 5 and touch Configure Touching the inside of this field will toggle the virtual keyboard 2 On the second boot loader screen Figure 3 6 enter the IP ...

Page 13: ...alarm with visible countdown timer if Snooze is enabled until audible alarms is reactivated The audible alarm will annunciate any time there is an active alarm displayed on the alarm If alarming or Snoozing is active and the filtered alarm list indi cates that no alarm is active any active state alarm or Snooze will be canceled automatically Automatic color coding allows for simple differ entiatio...

Page 14: ...enerated the UP arrow will scroll up to the previous alarm Touching the DOWN arrow will scroll down to the next alarm in the list 5 2 Alarm List Screen The Alarm List screen shows all filtered alarms in a list called the alarm log Multiple alarm entries are shown with a scroll bar to navigate through the alarm list UP and DOWN arrows will page up and page down on this screen ICON ACTION Displays t...

Page 15: ...ormation and if available the limit that was exceeded 5 3 Data Points Screen The Data Points screen is a view only screen that shows the list of all data points being monitored by the FSD In Figure 5 4 the Data Points screen name is dis played across the top of the screen in this example it is called Department Status This name is config ured under the Status Title parameter under FSD General Setu...

Page 16: ...es are active If no data point is selected when the details icon is touched a reminder will appear If a pointer has not been defined in the E2 applica tion a three dash result will appear If this three dash value is selected and the details icon is touched the following message will appear Figure 5 5 Detailed Data Point Information Figure 5 6 Detailed Information if the Data Point Failed Figure 5 ...

Page 17: ...iguring param eters Touch OK to save and exit to the Home screen Cancel to discard changes and exit to the Home screen 5 4 1 Alarms Tab Configure alarm information on the Alarms tab with the following parameters Show RTN Alarms Show Reset Advisories Display Asset Alarm Show Notices Filter Advisories Sort Data Points Audible Alarm settings Set snooze delay in minutes Set minimum alarm priority Thes...

Page 18: ...ow Notices This notice setting determines whether the FSD will display notices along with other types of adviso ries or whether these notices will be filtered out of the FSD Enable this box to show Notices in the alarm list uncheck to filter out 5 4 1 5 Filter Advisories This setting causes the FSD to display only advi sory information of points that are included in the monitored data point list A...

Page 19: ...The FSD will point only to a single E2 at a site it will not poll multiple controllers for alarms For multiple E2s at a site enter the IP address of the alarm annunciator E2 If one E2 is located at a site enter the IP address for that single E2 5 4 2 2 E2 IP Port The E2 IP Port is the port number used by the FSD to connect with the E2 unit The port number in this field must match the FSD Client Po...

Page 20: ...utomatically if the device is idle for more than 10 minutes To change the backlight setting 1 Touch the tool icon and enter the pass code on the security screen as shown in Fig ure 5 10 2 Select the General tab and touch the Exit Application button Figure 5 17 3 A loader screen will appear Figure 5 18 Touch Exit Loader at the top right of the screen 4 The desktop screen will appear Figure 5 19 Pre...

Page 21: ...n off backlight while on external power setting and from the drop down list choose when the backlight will automatically turn off 6 To save your settings touch and drag the Display Properties window to the left until you see OK in the upper right corner Touch OK to save and return to the desktop screen Figure 5 20 Display Properties Window Backlight Settings ...

Page 22: ...nd string values for the Title Data Point in the Title Data Pt and Title Data Str fields respectively This will change the default Title Data Point details on the FSD Data Point screen Figure 5 4 If the Title Data Point parameters are not changed the FSD Data Points screen will use the default values set for these parameters i e the Global Data s OAT 6 Press F2 Next Tab to go the Data Pts setup an...

Page 23: ... Communications 8 Go to the Pts Names tab and enter a name for the data point Figure 6 4 A point name is the unique name given to the data point specified by the user and will be displayed on the FSD screen 9 After entering the data point enter a unique name in the Data Name field on this screen If no name is assigned the data point will be displayed in the default Controller Application Property ...

Page 24: ...oint to point run from a switch or hub to the controller see Table 7 1 for hub part num bers for ordering This is done with Category5 or better cable Maximum distance for a run of 10BaseT is 328 feet 100 meters 11 5 dB loss max The maximum number of controllers allowed on an IP subnet is 20 All E2 controllers that must communicate with each other must be on the same subnet Recommended Ethernet cab...

Page 25: ...s network type is used if the network will be connected to the store s LAN The E2 peer Ethernet network facilitates commu nications between E2 controllers These include at least the following Routing of messages between external entities such as UltraSite InSite Site Manager and non gateway E2 controllers Distribution of global data and other network variables such as system time controller identi...

Page 26: ...etwork Administrator for any additional information needed NOTE DHCP does not have to be enabled if you have the IP Address Subnet Mask and Primary Gateway settings Contact your IT Network Administrator for all IP configuration information If you do not have the IP configuration settings and there is a DHCP server on the network set DHCP Enabled to Yes and it will retrieve the informa tion from th...

Page 27: ...t only one alarm annunciator per network is al lowed To set up from the Main Menu 1 Press System Configuration 2 Press System Information 3 Press General Controller Info 4 Set Alarm Annunc field to Yes 9 Software Updates Updates to FSD application functionality will au tomatically be synched with the update of E2 s firm ware Any software the device runs will be retrieved from the configured E2 Fig...

Page 28: ...5 Transformer Output to Circuit Board 24VAC Maximum Current 1 0 amp Humidity 10 to 95 104 F 40 C relative humidity non condensing Operating Temp 32 to 122 F 0 to 50 C Storage Temp 4 to 140 F 20 to 60 C Dimensions Screen diagonal 3 5 Flush mounting plate 9 x 10 Mounting hole 9 x 8 Table 10 1 Facility Status Display Specifications ...