Operating Instructions

1. General Install

Connecting the input power cable, output load cable and communication wire according 

to the below figure.

HPR12K-00

 

AC INPUT

AC INPUT

AC INPUT

AC INPUT

Main DC Output

Aux. DC 

Output

I2C/PMBus

Communication

Main DC Output

AC Line Input

2. General Settings

Unless otherwise specified, when the PSON# switch is de-asserted (48V o/p is disabled).

 It is means Manual ON/OFF DIP switch SW1 should be default according to below table. 

And It must be checked before shipping.

Power Supplies 
Status

PSU 1#

PSU 2#

PSU 3#

PSU 4#

CH 1

CH 2

CH 3

CH 4

CH 5

CH 6

CH 7

CH8

OFF

Up

Down

Up

Down

Up

Down

Up

Down

Note 1. The status Down means set to ON position. The status UP means set to OFF position.

Note 2.  Programming Switch SW1 default settings: 
                     PSON switches : OFF 
                     PSKILL switches : ON

DIP switch SW1 setting as a default

Summary of Contents for HPR12K-00

Page 1: ...2 General Settings Unless otherwise specified when the PSON switch is de asserted 48V o p is disabled It is means Manual ON OFF DIP switch SW1 should be default according to below table And It must be checked before shipping Power Supplies Status PSU 1 PSU 2 PSU 3 PSU 4 CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7 CH8 OFF Up Down Up Down Up Down Up Down Note 1 The status Down means set to ON position The st...

Page 2: ...e DIP switch CH2 should be set to ON as a default Incase if CH2 is set to off Power supply is slot 1 will not turn on even if CH1 is set to ON position Power Supplies Status PSU 1 PSU 2 PSU 3 PSU 4 CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7 CH8 ON Down Down Down Down Down Down Down Down OFF Up Down Up Down Up Down Up Down Note The status Down means set to ON position The status UP means set to OFF positio...

Page 3: ...stor internal to the power sup ply The power supply fan s shall operate at the lowest speed Signal Type Accepts an open collector drain input from the system Pulled up to the 3V3sb located inside the power supply PSON Low ON PSON Open OFF MIN MAX Logic level low power supply ON 0 V 0 4 V Logic level high power supply OFF 2 40 V 3 40 V Source current Vpson low 4 mA Power up delay T pson_on_delay 5m...

Page 4: ...ec P N 13866002800 Pins Landwin 2053T011P Table 4 PMBus Output Connector Figure 3 Connector CN1 Signal Name Description Pin Qty Pin Number s SCL Serial Clock Signal 1 4 SDA Serial Data Signal 1 2 Ishare Load Share Bus 1 7 5Vsb 5Vsb External Bus 1 1 Sys_GND Secondary Return 1 3 Unused 5 5 6 8 9 10 Table 5 Output Connection Definitions for PMBus 5 3 5V Stand By Auxiliary Output CN2 Self Connector Ma...

Page 5: ...ut for Unit 3 1 8 UNIT4_DCOK PWOK Power OK output for Unit 4 1 9 UNIT1_ACOK AC input present for Unit 1 1 10 UNIT2_ACOK AC input present for Unit 2 1 11 UNIT3_ACOK AC input present for Unit 3 1 12 UNIT4_ACOK AC input present for Unit 4 1 13 UNIT1_PSON Power enable input for Unit 1 1 15 UNIT2_PSON Power enable input for Unit 2 1 16 UNIT3_PSON Power enable input for Unit 3 1 17 UNIT4_PSON Power enab...

Page 6: ... and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2010 Emerson Electric Co EmersonNetworkPower com Embedded Computing Embedded Power Monitoring Outside Plant Power Switching Controls Precision Cooling Racks Integrated Cabinets Services Surge Protection Emerson Network Power The global leader in enabling business critical continuity AC Power Connectivity DC...

Reviews: