Options—Installation
17
4.5.2
Full-Height PDU Mounting Brackets
Three models of full-height PDU mounting brackets may be installed for a greater range of mounting
options. For standard positioning of a PDU, the fixed type can be used to place a PDU in either rear
corner of the rack. The inset PDU mounting bracket permits mounting a PDU nearer the side of the
cabinet, essentially recovering unused space. The adjustable PDU mounting bracket can be used to
mount a PDU at varying distances from the front or rear of the rack.
Available full-height PDU mounting brackets are:
• 42U, 4" wide: fixed PDU, Part # 539486G1L; inset PDU, Part # 542919G1L; adjustable PDU,
• 42U, 8" wide: fixed PDU, Part # 540084G1L
• 45U, 4" wide: fixed PDU, Part # 539487G1L; inset PDU, Part # 543002G1L; adjustable PDU,
• 45U, 8" wide: fixed PDU, Part # 540085G1L
To install a full-height PDU bracket:
1.
Position the full-height PDU mounting bracket for installation; refer to Figure 14 for placement.
2.
Hold the PDU bracket in place and insert and tighten the fasteners. The fastener used varies
depending on the PDU bracket and PDU:
• Fixed, full-height PDU mounting bracket: use mechanical, quarter-turn fasteners.
• Inset, full-height PDU mounting bracket: with Liebert MPX
™
PDU, use M5 hardware and
spring nuts; with Liebert MPH
™
PDU use M5 hardware and spring nuts; with Knurr DI-STRIP
®
PDU, use mechanical, quarter-turn fasteners; the center depth support must be removed from the
cabinet before installing this type of bracket, regardless of the type of PDU to be mounted.
• Adjustable, full-height PDU mounting bracket: with Liebert MPX PDU, use M5 hardware
and spring nuts; with Liebert MPH PDU or Knurr DI-STRIP PDU, use mechanical, quarter-turn
fasteners.