Installation
29
Liebert
®
APS
™
Configuring the Bypass Voltage
The UPS bypass voltage is factory-set to 208V (the jumper copper bar has been installed). Should the
user have a utility supply of 200V/220V/230V/240V, the bypass voltage jumper must be changed to
ensure correct output voltages when in bypass mode. Configuring the bypass voltage jumper settings
are shown in
Figures 34
and
35
. Refer to
Table 7
for the proper setting according to the AC mains
voltage configuration.
Figure 34 Setting bypass voltage jumper (default: 208VAC)
Figure 35 Setting bypass voltage jumper (200/220/230/240VAC)