Operator Control and Display Panel
Liebert
®
e
XM
™
42
6.2
Mimic Display Indicators
Figure 27 Mimic display indicators location
Mimic indicators show the operational status of the Liebert
e
XM by their color—green, amber or
red—and whether they are ON (solid), flashing or OFF.
Table 14
provides a guide to interpreting the
various states of the indicators.
Table 14
Mimic display status indicators
Indicator
(see Figure 27)
Green
Flashing Green / Amber
Red
Off
1. Rectifier
Load on Rectifier
Flashing Green: Utility normal,
but rectifier not operating
Rectifier fault
Rectifier is normal, but utility
is abnormal
2. Battery
Battery Powering
the Load
Flashing Green: Battery
pre-warning (low battery)
Battery or battery
converter abnormal*
Battery and converter are
normal, and battery is not
discharging
3. Bypass
Load on Bypass
Power
—
Bypass out of
normal range
Bypass Normal
4. Inverter
Inverter Powering
the Load Normally
Flashing Green: Inverter on
standby
Inverter fault
Inverter normal but Off
5. Load
UPS output On
—
UPS output overloaded
UPS has no output power
6. Status
No Alarms—UPS
Working Normally
Amber: UPS has a general
alarm
UPS has a serious alarm
—
* Battery or battery converter abnormal events include these event messages (see
Table 38
in
Appendix B - UPS Status Messages
): No
Battery, Battery Replaced, Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
Reflector
Indicator
Bypass
Indicator
Battery
Indicator
Status
Indicator
Load
Indicator
Inverter
Indicator