UPS Electrical Characteristics
Refer to additional circuit breaker notes in
3.2.7 - Accessory Fuses and Back-Feed Breaker
Wiring
.
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect
breaker must be provided for AC input, DC input and AC output. Recommended cable sizes are
suitable for operation at a maximum temperature of 104°F (40°C).
Table 23
UPS currents and terminals—Input (for single-input unit, 208V operation)
Unit
Rating
Nominal
Input Current
Maximum
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, Total
Copper
Wire
Aluminum
Wire
60
178
205
300
M12
400
(2) 3/0
(2) 4/0
80
237
273
350
M12
460
(2) 4/0
(2) 300 kcmil
100
297
341
450
M12
610
(2) 350
(2) 400 kcmil
Table 24
UPS currents and terminals—Input (for dual-input unit only, 208V operation)
Unit
Rating
Nominal
Input Current
Maximum
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current Total
Copper
Wire
Aluminum
Wire
60
178
205
300
M12
400
(2) 3/0
(2) 4/0
80
237
273
350
M12
460
(2) 4/0
(2) 300 kcmil
100
297
341
450
M12
610
(2) 350
(2) 400 kcmil
Table 25
UPS currents and terminals—Bypass input (for dual-input units, 208V operation)
Unit
Rating
Nominal
Input Current
OCP Device
Rating
Bolt Size
75°C Wire
Current, total
Copper
Wire
Aluminum
Wire
60
167
225
M12
285
(1) 300
(2) 2/0
80
222
300
M12
400
(2) 3/0
(2) 4/0
100
278
350
M12
460
(2) 4/0
(2) 300 kcmil
Table 26
UPS currents and terminals—Output 208V
Unit
Rating
Nominal Output
Current
OCP Device
Rating
Bolt
Size
75°C Wire
Current, total
Copper
Wire
Aluminum
Wire
60
167
225
M12
285
(1) 300
(2) 2/0
80
222
300
M12
400
(2) 3/0
(2) 4/0
100
278
350
M12
460
(2) 4/0
(2) 300 kcmil
Table 27
AC/AC efficiency, loss and air exchange
AC/AC Efficiency
Data
Normal Mode (dual conversion), %
95.5 maximum
Inverter Efficiency (DC/AC) (battery at nominal voltage 288VDC and full-rated linear load)
Rated Power, kVA
60-100
Battery Mode, %
94.8, Maximum
Heat Losses and Air Exchange
Rated Power, kVA
60
80
100
Normal Mode, kW
2.7
3.6
4.5
No Load, kW
0.9
1.2
1.5
Maximum forced air cooling
(front intake, rear exhaust), L/sec (m
3
/hr)
96 (346)
128 (462)
160 (575)
Heat Dissipation, BTU/Hr (kWH)
Without Transformer
9213 (2.7)
12,284 (3.6)
15,354 (4.5)
Summary of Contents for Liebert eXM
Page 1: ...Liebert eXM User Manual 60 100kVA 50 60Hz ...
Page 2: ......
Page 8: ...vi ...
Page 89: ...Maintenance 81 Liebert eXM NOTES ...
Page 90: ...Maintenance Liebert eXM 82 ...
Page 91: ......