Specifications and Technical Data
Liebert
®
e
XM
™
68
Table 28
Rectifier input
Parameter
60-100kVA
AC Input Parameters
50/60Hz, 3-Phase, 4-Wire Plus Ground
Rated AC Voltage
208/120V
220/127V
Input Voltage Range, Startup/Operating
177-253VAC
187-264VAC
Input Voltage Range, Operating
*
125-253VAC
132-264VAC
Frequency
50 or 60HZ (40-70Hz Range)
Power Factor
0.99 Full Load, 0.98 Half Load
UPS Capacities, kVA
60/80/100
Input Current (A), Rated
178/237/297
168/224/281
Input Current (A), Maximum
205/273/341
194/258/322
THD
5% Full Load
* Derated operation for reduced input voltage: 208V Operation (125-177VAC), 220V Operation (132-187VAC)
Table 29
Recommended lug sizes (compression type) M12, 1/2" bolt
Cable Size
T&B Copper
Two Hole
T&B Aluminum
Two Hole
#6AWG
256-030695-868
—
#4AWG
256-030695-733
—
#2-3AWG
54811BE
—
#1AWG
54857BE
—
#1/0AWG
256-30695-593
—
#2/0AWG
54862BE
60238
#3/0AWG
54864BE
60244
#4/0AWG
54866BE
60250
250kcmil
54868BE
60256
300kcmil
54870BE
60262
350kcmil
54872BE
60267
400kcmil
54874BE
60269
500kcmil
54876BE
60273
600kcmil
54878BE
60275
700kcmil
54879BE
60277
750kcmil
54880BE
60278
Table 30
Battery cabinet system—UPS and Battery Cabinet
UPS Rating, kVA
Battery Cabinet Breaker
Maximum Battery Current, A
Battery Cabinet Size, mm
60-100
465A
465
600, 880