Maintenance
79
Liebert
®
e
XM
™
Bypass Phase Reversed
The phase sequence direction of bypass voltage is reversed.
Normally, the phase of Phase B lags 120 degrees behind Phase A, and the phase of Phase C
lags 120 degrees behind Phase B.
Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if
it is found to be in error. Contact Liebert Services at 800-543-2378 for assistance.
Load Impact Transfer
A transfer to bypass occurred due to a large step load. The UPS should recover automatically.
Turn on connected equipment in sequential order to reduce the step loading of the inverter.
Transfer Timeout
The load is on bypass power due to excessive number of transfers that occurred within the last
hour.
The UPS will recover automatically and will transfer the load back to inverter power within an
hour.
Load Sharing Fault
UPS working within a parallel system are not sharing load current correctly. Contact Liebert
Services at 800-543-2378 for assistance.
DC Bus Abnormal
Shut off inverter due to abnormal DC bus voltage.
Contact Liebert Services at 800-543-2378 for assistance.
System Transfer
The whole paralleled UPS system transferred to bypass at the same time. This message will
appear on the UPS which passive transfer to bypass.
DC Bus Overvoltage
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.
Check whether there is a fault in rectifier side. If no, then check whether overload occurs.
Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Services at 800-
543-2378 for assistance.
LBS Active
The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus
configuration.
Battery ground fault
Battery ground fault from dry contact signal. Contact Liebert Services at 800-543-2378 for
assistance.
Inverter turned On
manually
Manual Turn On via front panel
Inverter turned Off
manually
Manual Turn Off via front panel
EPO
Emergency Power Off
Transfer Confirm
Interrupted Transfer Confirm
Transfer Cancel
Interrupted Transfer is cancel
Unit Off Confirm
Unit Turned Off Confirm
System Off Confirm
System Turned Off Confirm
Fault Reset
Fault Reset
Alarm Silence
Alarm Silence
Turn On Fail
Turn On Fail
Alarm Reset
Audible Alarm Reset
Bypass Mode
UPS in Bypass Mode
Normal Mode
UPS in Normal Mode
Battery Mode
UPS in Battery Mode
Output Disabled
UPS Output Disabled
Maint. Disconnect Closed
Maintenance Disconnect Closed
Reserved
—
Output Disconnect Open
Output Disconnect Open
Battery Reverse
Connect the battery again and check the wiring of batteries.
No Battery
Check the battery and the wiring of batteries.
Auto start
After UPS was shutdown at EOD, inverter auto starts when utility is restored.
BCB closed
BCB closed from dry contact signal.
Table 38
UPS status messages
(continued)
Event Message
Description / Suggested Action (if any)