21
09: Programmable output setting
Note
:
This function is not supported by the Rack model with parallel function.
Interface
Setting
Parameter 2:
Set programmable output. You may choose the
following three options:
ON:
Programmable output is manually switched on timelessly.
OFF:
Programmable output is manually switched off. However, if
UPS restarts, this setting will automatically go to “ATO” status.
ATO:
Programmable output is automatically turned on or cut off
according to battery or load status. When the battery voltage is
lower than the setting point, or shutdown time arrives, the
programmable output will be cut off automatically. After the utility
is recovering, the output will turn on automatically. If overload
happens, the programmable output also will be cut off
automatically. If it happens 3 times, the programmable output
will be cut off until it is manually switched on.
10: Programmable output shutdown voltage setting
Note
:
This function is not supported by the Rack model with parallel function.
Interface
Setting
Parameter 2:
Set shutdown voltage for programmable output.
Setting range is from 11.2 to 13.6. If the battery voltage is less
than the setting point, the programmable output will be cut off.
The default value is 11.2V.