Operation

14

Figure 11 Menu tree

Start 

Window

System 

Status

Main

Setup

Control

Contrast 

Set

Battery 

Test

Alarm 

Control

Turn UPS

 On/Off

Status

Log

About

Version

Language

Tag 

Number

UPS 

Address

DC Start

Battery 

Test 

Interval

Battery 

Pack

Audible 

Alarm

Output 

Voltage

Clear

Event Log

IP

Types

Battery 

Test

Battery 

Test

Battery 

Test

Parallel 

Menu

Parallel 

Model

Summary of Contents for Liebert GXT3 1000 BA

Page 1: ... l un I Jet _________ __ ИБП Liebert GXT3 T 10000 ВА руководство пользователя Юниджет Постоянная ссылка на страницу https www uni jet com catalog ibp on line ibp liebert upstation gxt3 ...

Page 2: ...More user manuals on ManualsBase com AC Power For Business Critical Continuity Liebert GXT3 10000T220 User Manual 10kVA 50 60 Hz 120 208 220V ...

Page 3: ...More user manuals on ManualsBase com ...

Page 4: ...and Isolating Devices 8 3 4 External Electrical Connections 9 3 5 Connecting Utility and Load 9 3 6 Terminal Blocks for UPS 9 3 6 1 Input and Output Connection Requirements 10 3 7 Connecting Power Cables 11 3 8 External Battery Cabinets 11 4 0 OPERATION 12 4 1 Block Diagram 12 4 2 Control Panel 13 4 2 1 Controls and Messages 13 4 2 2 Battery Setup Parameters 16 4 2 3 Warning Indicators 16 4 2 4 Fa...

Page 5: ...npacking 6 Figure 4 Side view 9 Figure 5 Single source input supply input and output connections 9 Figure 6 Dual source input supply input and output connections 10 Figure 7 Hardwire terminals 10 Figure 8 Liebert GXT3 10000T220 with External Battery Cabinet 11 Figure 9 System block diagram 12 Figure 10 Control Panel 13 Figure 11 Menu tree 14 Figure 12 Dry contact pin layout 21 TABLES Table 1 Overv...

Page 6: ...s do not electrically isolate internal parts Under no circumstances attempt to gain access internally due to the risk of electric shock or burn Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS performance alters in use Refer all faults to your dealer Servicing of batteries should be performed or supervised by personnel...

Page 7: ... 3 0 Installation In emergencies e g damaged case controls or power cables penetration of liquids or for eign matter switch off the device and contact the appropriate customer service representa tive Do not connect equipment that will overload the UPS e g laser printers or vacuum clean ers or demand DC current e g half wave rectifiers When cleaning the unit follow the instructions in 5 0 Maintenan...

Page 8: ...ense The Liebert GXT3 series complies with the requirements of EMC Directive 2004 108 EC and the published technical standards Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson NOTICE Operating the Liebert GXT3 in residential areas may cause radio interference that the user must to correct at his own expense Information for ...

Page 9: ...ronic equipment operates best from sinewave power The liquid crystal display is used for controlling operation of the UPS as well as monitoring its status condition alarm status and history For ease of use the Liebert GXT3 10000T220 features a light emitting diode LED display to indicate operational status It also provides self diagnostic tests a combination On Alarm Silence Battery Test button a ...

Page 10: ...ower UPS with Integrated Battery Liebert GXT3 10000T220 10000VA 90000W Battery Cabinet Liebert GXT3 240TBATTCE Control Panel Liquid Crystal Display Push Button Controls Ventilation Louvers Bypass Circuit Breaker Hardwire Input and Output Connectors Protective Cover Shown Liebert IntelliSlot Communication Card slot Dry Contacts Input Circuit Breaker REPO Maintenance Bypass Breaker cover removed for...

Page 11: ...000T220 near its installation site 2 Unlock all the snaps securing the shipping case to the shipping pallet 3 Lift the shipping case off the UPS 4 Remove the EPE packing cushions from around the Liebert GXT3 10000T220 5 Remove the ramp from the front and slip into the slot on the front of the shipping pallet 6 Roll the UPS off the shipping pallet Figure 3 Unpacking Storage If the UPS will be store...

Page 12: ...Area The area where the Liebert GXT3 10000T220 is to be placed must have sufficient space for installation procedures and for routine maintenance The UPS is narrow enough to pass through standard doorways 2 6 Floor Loading Ensure that the floor where the UPS will be installed will support the unit s weight see Table 9 for the unit s weight 2 7 Inventory List CD containing Liebert MultiLink shutdow...

Page 13: ...position output power is available immediately upon application of AC input Table 2 Connection data Description Units Liebert GXT3 10000T220 Connector size AWG mm2 6 10 Max input current Arms 56 Input cable size and neutral AWG mm2 6 10 Max output current Arms 56 Output cable size and neutral AWG mm2 6 10 Ground Earth Cable Size AWG mm2 6 10 Terminal Torque lb in Ncm 10 113 Cable must be 90 C copp...

Page 14: ...00T220 is supplied by single phase utility connect the live phase to input L1 3 6 Terminal Blocks for UPS Figure 5 Single source input supply input and output connections WARNING Before removing electric protective panel ensure that the UPS is isolated NOTE Once installation has been completed adjust leveling feet to prevent the UPS from moving CAUTION Power is connected through the input breaker ...

Page 15: ...de in the building grounding electrode system If the grounding electrode conductor must be protected non metallic conduit is recommended If metal conduit must be used bond both ends of the conduit to the grounding electrode conductor Conduit is not an acceptable grounding electrode conductor The utility may be derived from a single phase or three phase source The line to ground voltages are depend...

Page 16: ...Liebert GXT3 10000T220 is supplied with each battery cabinet Open the breaker before making battery cable connections Plug one end of this cable into the UPS and the other end into the battery cabinet slotted fittings on each end ensure that the connection is properly made If your UPS has an integrated battery a compensating current may occur during connection Once both ends of the cable have been...

Page 17: ... with separate breakers utility and bypass rectifier booster inverter and charger electronic bypass 2 position Maintenance Bypass Breaker UPS and BYPASS integrated battery Figure 9 System block diagram TVSS EMI RFI Filters Rectifier PFC DC to DC Converter Inverter Isolation Transformer Battery Battery Charger L1 N L1 N X1 X3 X4 X2 Output Input Dynamic Bypass V bp G G ...

Page 18: ... 2 1 Controls and Messages Lighted LEDs UPS ON UPS is in normal online operation BYPASS Load is supplied by the utility via automatic bypass BATTERY Load is supported by the battery FAULT A problem has developed within the UPS Flashing LED When the BYPASS LED is flashing the utility is out of tolerance NOTICE Risk of loss of power to connected load Can cause equipment damage Never switch the UPS O...

Page 19: ... Main Setup Control Contrast Set Battery Test Alarm Control Turn UPS On Off Status Log About Version Language Tag Number UPS Address DC Start Battery Test Interval Battery Pack Audible Alarm Output Voltage Clear Event Log IP Types Battery Test Battery Test Battery Test Parallel Menu Parallel Model ...

Page 20: ...etup Menu Setting item Setting level 1 Audible alarm Disable Enable Output voltage 208 220 230 240V Battery pack 1 3 1 Battery Test interval DC start Disable Enable Tag Number 00000 99999 Language English French Spanish German Italian Russian Logging Menu Event and time Clear event log Max 4 fault event record Firmware Version Type of UPS Liebert GXT 10KVA Liebert GXT3 10000T220 Capacity 10KVA Int...

Page 21: ...ery Test Battery Test Report Contrast Darker Lighter Battery Test Report Test in progress Test to Low Battery Test OK Cancel Battery test Test fail Battery Test report Test stop by user Test unknown 1 For setup parameters regarding battery pack quantity refer to 4 2 2 Battery Setup Parameters Table 4 Battery setup parameters Parameter Internal Battery X Integrated Quantity External Battery Cabinet...

Page 22: ...um of 4 fault events may be displayed in this window All fault displays include the nature of the fault event and the time it occurred the time is relative to the UPS operating time Display faults The various possible fault indicators are listed in the following table Table 6 Fault indicators Fault Cause Corrective steps 1 DC BUS fault Call customer service 2 Inverter fault Call customer service 3...

Page 23: ...Control and press the Enter key 2 Select Turn UPS On Off and press the Enter key The LCD displays Turn UPS to BYPASS 3 Press the Enter key to switch off the inverter 4 Open any external circuit breakers fused disconnects connecting the load if present 5 Switch both Input circuit breakers to the Off position 6 Ensure all circuit breakers fused disconnects upstream of the UPS are open 7 Ensure that ...

Page 24: ... to Bypass mode 5 A single acoustic signal confirms the operation 6 Select Turn UPS On Off and press OK to place the UPS back in Normal Mode operation The UPS performs the test during Start up 4 8 2 Battery Test 1 Press the Menu button 2 Select SETUP and press OK 3 Select BATT TEST and press OK A single acoustic signal confirms the operation and the load will be supplied by the battery If the test...

Page 25: ...bient temperature of 25 C but is also dependent on the frequency and duration of utility failures The BATTERY TEST see 4 8 2 Battery Test should be run periodically 6 to 12 months to ascertain the general condition of the batteries and ensure maximum run time 5 2 Storage For extended storage at ambient temperatures cooler than 25 C 77 F the batteries should be charged for 24 hours once every six m...

Page 26: ...n Set 3 Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the event history log NOTE Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown The current limited source 12VDC 50mA will be available from UPS The connection to UPS for remo...

Page 27: ...ard Liebert IntelliSlot 485 Card The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built in shutdown for AS 400 systems The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system Follow instructions prov...

Page 28: ...t MultiLink software on four computers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built in shutdown for AS 400 systems 6 4 Remote Emergency Power Off The UPS is equipped with a Remote Emergency Power Off REPO connector The user must supply a means of interfacing...

Page 29: ... mains voltage present Have utility mains inspected by a qualified technician UPS on LED does not illuminate when utility mains voltage present acoustic alarm active at intervals Input fuse defective or input circuit breaker tripped Replace with fuse of same type or switch on circuit breaker If the problem persists contact technical support FAULT LED illuminates alarm sounding constantly UPS error...

Page 30: ...10 seconds 105 130 1 minute Battery Parameters Type Valve regulated non spillable lead acid Quantity x V 20 x 12V Battery Mfr Part CSB HR1234R or Panasonic UP RW1245 Backup Time See Table 11 Recharge Time Internal Batteries 3 hr to 90 capacity after full discharge into 100 load Bypass Protection Limits Maximum Bypass Current 50A Disable Bypass Operation If input voltage exceeds 10 of the nominal v...

Page 31: ...Table 11 Environmental Operating Temp F C 32 to 80 0 to 27 Storage Temp 5 to 104 15 to 40 Transportation Temp F C 5 to 122 15 to 50 Relative Humidity 0 95 non condensing Operating Elevation Up to 3281 ft 1000m at 80 F 27 C without derating Agency Safety UL 1778 c UL Listed Transportation ISTA Procedure 1B Table 11 Typical battery run times for the Liebert GXT3 10000T230 Number of Batteries Battery...

Page 32: ...TRATION To register for warranty protection Visit the Quick Links section of Liebert s Web site at http www liebert com Click on Product Warranty Registration and fill in the form If you have any questions please contact us at US 800 222 5877 Outside the US 614 841 6755 liebert upstech emerson com ...

Page 33: ... change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upstech emerson com 800 222 5877 Outside North...