Troubleshooting
Liebert
®
GXT4
™
User Manual
60
7.1.2
Audible Alarm
An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating
status. The audible alarm will sound as described in
.
7.2 Troubleshooting
In the event of an issue with the UPS, refer to
to determine the cause and solution. If the fault
persists, contact Emerson
®
Channel Support.
Table 7-2
Audible alarm description
Condition
Alarm
Battery discharge
Half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
Half-second beep every half second
Battery replacement
2-second beep every 2 minutes
Battery loss
Continuous
Wiring problem (loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 60 seconds
Table 7-3
Troubleshooting table
Problem
Cause
Solution
UPS fails to start
UPS is short-circuited or
overloaded
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in
output receptacles. Ensure loads are not defective or shorted internally.
Batteries are not charged
enough or not connected
Check to ensure the internal battery is connected. If it is not, make the
connection and try to start the unit. If the battery is connected, leave the
UPS connected to input power for 24 hours to recharge batteries, then try
to start the unit.
Battery indicator
is illuminated
UPS is not plugged in
UPS is operating from battery mode. Ensure UPS is securely plugged
into the wall receptacle.
UPS input protection fuse has
blown/opened
UPS is operating from battery mode. Save data and close applications.
Replace UPS input fuse, then restart UPS.
Mains power is out of tolerance
UPS is operating from battery mode. Save data and close applications.
Ensure mains supply voltage is within acceptable limits for UPS.
UPS has
reduced battery
backup time
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 hours to recharge
batteries.
UPS is overloaded
Check load level indicator and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age
Replace batteries. Contact your local dealer, Emerson representative or
Emerson Channel Support for replacement battery kit.
Battery indicator
is flashing.
Battery source is not available;
continuous horn.
Check battery connections, completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS is running, it will be
detected when the next battery test is performed.
Bypass indicator
is flashing.
Because the voltage or
frequency is outside acceptable
limits, the bypass is disabled.
The AC input powers the PFC input and serves as the bypass source. If
the AC is present but the voltage or frequency exceeds the acceptable
range for safe operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is unavailable.
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......