Installation
25
Liebert
®
GXT4
™
User Manual
Figure 2-7 Distribution box electrical connections diagram
2.6.5.1 Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share
the same conduit. Emerson recommends using strain relief when installing the wire.
Table 2-2
Electrical specifications
UPS Model
Recommended
(Maximum) External
Overcurrent Protection
Recommended Wire
(Including ground wire)
(75°C copper wire)
Maximum Wire
Accepted by
Terminal Block
Terminal
Tightening
Torque
GXT4-5000RT208
GXT4-6000RT208
GXT4-6000RTL630
30A
10AWG (4mm
2
)
8AWG (6mm
2
)
20 in-lb
(2.26 Nm)
GXT4-8000RT208
GXT4-10000RT208
60A
6AWG (10mm
2
)
4AWG (16mm
2
)
Utility
Input
External
Branch CB
Output
Distribution
POD
Input
CB
Output
CB
Input
Indicator
Output
Indicator
Maintenance
Bypass Breaker
UPS
Utility
Input
External
Branch CB
Optional
Output
Distribution
Plate
Input
CB
Output
CB
Input
Indicator
Output
Indicator
Maintenance
Bypass Breaker
UPS
Output
Terminal
Block
Distribution Box Electrical Connections
for 5000 and 6000VA Models
Distribution Box Electrical Connections
for 8000 and 10,000VA Models
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......