Communication
47
Liebert
®
GXT4
™
User Manual
5.0 Communication
This section describes the communication ports on the rear of the UPS:
• Liebert IntelliSlot
®
port
• USB port (standard B-type)
• Terminal Block Communication
5.1 Liebert IntelliSlot Communication Cards
The Liebert IntelliSlot port accepts four optional cards:
• Liebert IntelliSlot Web Card (IS-WEBCARD)
• Liebert IntelliSlot Relay Card (IS-RELAY)
• Liebert IntelliSlot MultiPort Card (IS-MULTIPORT)
• Liebert IntelliSlot Unity Card (IS-UNITY-DP)
The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and
delivers support for Liebert MultiLink
®
shutdown software.
The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that
have Liebert MultiLink installed.
The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network
and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external
temperature, humidity and contact closure inputs using external sensors.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink
®
, the UPS or any
additional ancillary product for the Liebert GXT4. These instructions are available at:
5.1.1
Liebert MultiLink
Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of
an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.
Liebert MultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via
terminal block or over the network via SNMP using the Liebert IS-WEBCARD. An optional Liebert MultiLink
license kit permits shutting down multiple computers that are protected by the UPS.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert
MultiLink License Kits, visit the Liebert Web site (
) or contact your local Emerson
®
representative.
!
CAUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be
segregated and run separate from all other power cables.
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......