Maintenance
Liebert
®
GXT4
™
User Manual
54
6.1.1
Battery Replacement Procedures
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the
UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or
Emerson representative to obtain the pricing of the appropriate replacement battery pack.
1. Remove the front plastic bezel cover from the UPS.
2. Loosen and remove the 6 screws on the battery door, as shown in
.
3. Lay the battery door and screws aside for reassembly.
Figure 6-1 Removing the front bezel cover and battery door
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in
Figure 6-2 Disconnecting the battery plug and battery receptacle (front view)
!
CAUTION
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to
the instructions.
Front Bezel
Battery Door
Screws, 6
Battery
Connector
Battery
Receptacle
Battery
Receptacle
Battery
Connector
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......