Specifications
63
Liebert
®
GXT4
™
User Manual
8.0 Specifications
Table 8-1
UPS specifications—5000, 6000, 8000 and 10,000 models
Model Number
GXT4-
5000RT208
GXT4-
6000RT208
GXT4-
8000RT208
GXT4-
10000RT208
Model Rating
4000W/5000VA
4800W/6000VA
7200W/8000VA
9000W/10000VA
Dimensions, Rack Mount, W x D x H
Unit, in. (mm)
16.9 x 26.1 x 6.8 (430 x 662 x 173)
16.9 x 26.5 x 10.3 (430 x 672 x 261)
Shipping, in. (mm)
35 x 27 x 26 (889 x 686 x 661)
35 x 27 x 32 (889 x 686 x 813)
Weight lb (kg)
Unit, lb (kg)
131.8 (59.8)
212.7 (96.7)
Shipping, lb (kg)
202.8 (92)
297.6 (135)
Input AC Parameters
Nominal Operating Frequency
50 or 60Hz (Factory Default is 60Hz)
Factory Default VAC
120/208VAC at 120 degrees
120/208VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle
120 degrees
120 degrees
Allowable Input Phase Angle
120, 180, 240 degrees, auto-sensing on application of alternating current
(Restrictions for L-N voltages other than 120VAC)
Factory Default L1-N, L2-N VAC
120 VAC nominal
User Configurable L1-N, L2-N VAC
100/110/115/120VAC (can be modified with configuration program)
Input Frequency w/o Battery Operation
40 - 70 Hz
Input Power Connection
Hard-Wired Terminal Block 3W + G (L-L-N-G)
L1-N, L2-N Maximum Allowable VAC
150VAC
Output AC Parameters
Factory Default VAC
120/208VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle
120 degrees
Allowable Output Phase Angle
120, 180, 240 degrees, auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC
120VAC nominal
User Configurable L1-N, L2-N VAC
100/110/115/120/127VAC, ±2%
L1-N, L2-N, Operating Load Range
105% to 130%
1 Minute
131% to 150%
10 seconds
151% to 200%
1 second
>200% (impact load)
At least 5 cycles
Bypass Protection Limits
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation
When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C)
32 to 104 (0 to 40)
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1E
Summary of Contents for Liebert GXT4-10000RT208
Page 1: ...Liebert GXT4 UPS 208 V 5000 VA 10 000 VA 6000RTL630 User Manual ...
Page 2: ......
Page 12: ...Glossary of Symbols Liebert GXT4 User Manual 4 Page intentionally left blank ...
Page 24: ...Product Description Liebert GXT4 User Manual 16 Page intentionally left blank ...
Page 36: ...Installation Liebert GXT4 User Manual 28 Page intentionally left blank ...
Page 52: ...Operation and Display Panel Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 70: ...Troubleshooting Liebert GXT4 User Manual 62 Page intentionally left blank ...
Page 79: ......