Communication
Liebert
®
GXT4
™
User Manual
42
5.3.2
Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static
switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS
will still be active.
Battery Mode Shutdown can be performed locally or remotely:
• Local Battery Mode shutdown can be performed by shorting pins3 and 4.
• Remote Battery Mode Shutdown can be performed using a switch mounted in a remote location and
connected to pins 3 and 4.
5.3.3
On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery this dry contact will be closed.
5.3.4
Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the
battery and has reached the Low Battery Warning time selected in the configuration program, this dry
contact will be closed.
NOTE
Remote Power Off will be performed by NO contact.
A current-limited source (+12 VDC, 50 mA) will be available from UPS.
The connection to the Liebert GXT4 for remote connection will be via terminal block connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and
laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown
timer. This timer cannot be stopped once triggered. If the mains power returns during this
countdown, the Liebert GXT4 will still shut down and must remain shut down for 10 seconds.
Whether the UPS turns back On when the power is restored depends on the auto-restart setting.
NOTE
The rated values for the dry contacts for the On Battery and Low Battery signals are:
• Rated Voltage: 30 V (AC or DC)
• Rated Current: 300 mA
Summary of Contents for Liebert GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Page 2: ......
Page 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Page 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Page 67: ......