Specifications
57
Liebert
®
GXT4
™
User Manual
Using the configuration program, the user may specify the number of GXT4-240VBATT external battery
cabinets attached to the UPS. The factory default is programmed for internal batteries only.
shows the estimated run times at different loads.
Internal Battery
+ 4 External
Battery Cabinets
10%
910
824
574
20%
499
397
282
30%
363
297
179
40%
277
216
134
50%
225
173
106
60%
182
141
85
70%
148
118
71
80%
130
99
57
90%
118
90
48
100%
100
82
43
Internal Battery
+ 5 External
Battery Cabinets
10%
1143
1033
695
20%
626
498
345
30%
455
371
217
40%
345
268
164
50%
281
213
129
60%
224
176
106
70%
184
148
87
80%
163
125
74
90%
148
114
60
100%
125
103
55
Internal Battery
+ 6 External
Battery Cabinets
10%
1367
1248
826
20%
750
601
409
30%
547
448
257
40%
416
322
192
50%
338
256
151
60%
270
210
125
70%
217
177
106
80%
196
151
87
90%
178
138
75
100%
152
124
68
Table 8-4
Battery run time, minutes, all models (continued)
Number of
Batteries/Cabinets
Load Percent
of Capacity
230VAC RT Models
5kVA
6kVA
10kVA
Run times in this table are approximate. They are based on new, fully charged
standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS
loading. Run times listed above can vary by ±5% due to manufacturing variances of
the batteries.
Summary of Contents for Liebert GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Page 2: ......
Page 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Page 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Page 67: ......