Specifications
Liebert
®
GXT4
™
User Manual
56
Table 8-4
Battery run time, minutes, all models
Number of
Batteries/Cabinets
Load Percent
of Capacity
230VAC RT Models
5kVA
6kVA
10kVA
Internal Battery
10%
95
86
99
20%
42
38
44
30%
36
31
25
40%
29
23
17
50%
24
17
13
60%
18
13
10
70%
14
11
7
80%
12
9
6
90%
11
7
4
100%
9
7
4
Internal Battery
+ 1 External
Battery Cabinet
10%
273
249
209
20%
143
116
105
30%
107
86
63
40%
80
61
44
50%
64
45
34
60%
49
36
26
70%
38
29
21
80%
33
24
17
90%
29
21
14
100%
24
18
12
Internal Battery
+ 2 External
Battery Cabinets
10%
476
431
327
20%
254
207
164
30%
191
158
103
40%
146
113
76
50%
119
89
56
60%
94
69
44
70%
72
56
37
80%
63
47
29
90%
56
42
24
100%
47
37
22
Internal Battery
+ 3 External
Battery Cabinets
10%
689
627
450
20%
374
299
221
30%
274
226
141
40%
211
165
105
50%
173
130
82
60%
137
105
65
70%
111
88
53
80%
97
73
43
90%
88
64
37
100%
74
58
33
Run times in this table are approximate. They are based on new, fully charged
standard battery modules at a temperature of 25°C (77°F) with 100% resistive UPS
loading. Run times listed above can vary by ±5% due to manufacturing variances of
the batteries.
Summary of Contents for Liebert GXT4-10000RT230
Page 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Page 2: ......
Page 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Page 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Page 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Page 67: ......