Chapter 2 Installation 9
Liebert GXT4 UPS 700VA ~ 3000VA (230V) User Manual
Note
B1 includes inner member, front and rear members. They are interchangeable between left-hand or right-hand.
2. Remove inner member of each B1 by extending it to its outermost position, depressing the retaining latch and then
pulling out the inner member from B1, as shown in Figure 2-7.
Inner member
Pu
ll o
ut
Retaining latch
Front member
Rear member
Figure 2-7 Pulling out inner member from each B1
3. Determine the mounting position inside the rack inside the racks vertical rails.
Caution
Reduce the risk of tipping the rack by installing the Liebert GXT3 as low as possible in the rack.
4. Attach the rear member of each B1 to the rack vertical poles with two factory-supplied S2, as shown in Figure 2-8.
S2 (4 pcs)
Vertical pole
Rear member
Front member
Figure 2-8 Installing rear member of each B1
5. Extend the B1 by sliding the front member forward until it touches the rack’s front vertical poles (adjustable length:
18 inches ~ 32 inches (457mm ~ 813mm)). Use two S2 to fix each front member onto the front vertical poles through
the installation holes. Make sure that the two pieces of B1 are at the same mounting height on all four rack vertical
poles, as shown in Figure 2-9.