12 Chapter 2 Installation
Liebert GXT4 UPS 700VA ~ 3000VA (230V) User Manual
Table 2-1 Specification of input circuit breaker
Model
Rated circuit breaker
GXT4-700RT230 10A
GXT4-1000RT230 10A
GXT4-1500RT230 10A
GXT4-2000RT230 16A
GXT4-3000RT230 16A
GXT4-700RT230E 10A
GXT4-1000RT230E 10A
GXT4-1500RT230E 10A
GXT4-2000RT230E 16A
GXT4-3000RT230E 16A
1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT4.
Note
1. Distribute loads evenly across all receptacles to prevent overloading individual receptacles.
2. Output cable length should not exceed 32.8 ft (10m).
3. The priority load can be connected to the general output receptacle and fixed by a line buckle (see Figure 2-14) to prevent the
output cable from loosening and dropping.
Insert it into the fixing hole for line buckle
Hold the output cable
Figure 2-14 Line buckle
2. Insert the input cable of Liebert GXT4 into the input power connection.
2.5.2 Connecting Battery Cable
1. Switch Off the input breaker of the battery cabinet.
2. Take out the battery cable included with the battery cabinet.
3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect
the other end to any battery port on the rear panel of the external battery cabinet, as shown in Figure 2-15.
Figure 2-15 Connecting the battery cable
4. Switch on the battery breaker on the rear of the external battery cabinet.
5. Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected
to the Liebert GXT4. For approximate battery run time, see Table 9-4 in
Chapter 9 Specifications
.