38 Chapter 9 Specifications
Liebert GXT4 UPS 700VA ~ 3000VA (230V) User Manual
Table 9-3 Battery cabinet specifications
Parameter
Model Number
GXT4-48VBATT GXT4-48VBATTE
GXT4-72VBATT GXT4-72VBATTE
Used UPS model
GXT4-700RT230,GXT4-700RT230E
GXT4-1000RT230,GXT4-1000RT230E
GXT4-1500RT230,GXT4-1500RT230E
GXT4-2000RT230,GXT4-2000RT230E
GXT4-3000RT230,GXT4-3000RT230E
Dimensions, D
× W × H
in(mm)
Unit
19.7 × 16.9 × 3.3 (497 × 430 × 85)
23.7 × 16.9 × 3.3 (602 × 430 × 85)
Shipping
24.3 × 22.4 × 10.3 (617 × 570 × 262)
28.2 × 22.4 × 10.3 (717 × 570 × 262)
Weight, lb (kg)
Unit
57.3 (26)
57.3 (26)
83.8 (38)
83.8 (38)
Shipping
83.7 (38)
74.9 (34)
112.4 (51)
103.6 (47)
Battery
parameters
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
2 × 4 × 12V × 9.0Ah
2 × 6 × 12V × 9.0Ah
Battery Mfr./Part #
Panasonic/UP-RW1245; CSB/ HR1234W HR CSB/UPS 12460 F2
Backup Time
See Table 9-5
Environmental
Operating
temperature, °F (°C)
32 to 104 (0 to 40)
Storage
temperature, °F (°C)
19 to 122 (-15 to 50)
High ambient temperatures will reduce battery life.
Relative humidity
0% to 95%, non-condensing
Operating elevation
Up to 10,000 ft. (3000m) at 104ºF (40ºC) without derating
Storage elevation
50,000 ft. (15000m) maximum
Agency
Safety
IEC/EN 62040-1:2008, GS mark
RFI/EMI
FCC Part 15, Class A = CISPR22 Class B
Surge immunity
IEC 62040-2 2nd Ed2006
Transportation ISTA
Procedure
1A
Note:
No slide rails assemblies are included in the E model
Table 9-4 Operating temperature parameters
Ambient temperature, °C (°F)
25 ~ 30 (77 ~ 86)
30 ~ 35 (86-95)
35 ~ 40 (95 ~ 104)
Maximum output power factor derating @
maximum load
100% ~ 93%
93% ~ 86%
86% ~ 79%
Table 9-5 Battery run time
Number of batteries
Load
230Vac RT Models(Include E Models)
700VA 1000VA 1500VA 2000VA 3000VA
Internal battery
10% 105
90
77
77
74
20%
61 37 35 33 36
30%
37 30 23 21 21
40%
32 23 16 15 15
50%
27 17 11 11 11
60% 22
14
10
8
8
70% 18
11
6
6
6
80% 15
9
5
5
5
90% 13
8
4
4
4
100% 11
7
4
3
3
Internal b 1
external battery cabinet
10%
306 212 199 183 166
20%
182 151 133 124 121
30% 149
123
97
80
79
40% 130
100
72
41
53
50% 109
80
41
38
46
60%
98 68 38 34 39
70%
81 41 35 30 31
80%
72 39 32 25 26
90%
63 37 27 21 21
100%
41 35 23 17 18