Communication System Manual
UPS System: HIPULSE E
(Modbus/Jbus Interface)
Description of Protocol
(04/07)
Page 5-13
5.9
PROGRAMMING PARAMETERS
Address
Meaning
SIZE (BYTES)
Range / Resolution
Format
UPS MSS
40080
Rated voltage
2
Rotating
HEX note 1
Lower limit on
2
00:99 (V
in
%)
HEX
40081
rated input voltage
Upper limit on
2
00:99 (V
in
%)
HEX
40082
rated input voltage
Lower limit on
2
00:99 (V
in
%)
HEX
40083
rated output voltage
Upper limit on
2
00:99 (V
in
%)
HEX
40084
rated output voltage
40085
Rated frequency
2
Rotating
HEX note 1
40086
Deviation
2
0:9 (Frq %)
HEX
40087
Slew Rate
2
Rotating
HEX nota 1e 3
---
40088
Number of battery cells
2
190 : 210
HEX note 3
---
40089
Rated capacity
2
0:9999 (Ah)
HEX note 3
---
40090
End of cell discharge
2
150 : 170 1/10 V
HEX note 2 e 3
---
Pre-alarm for end of
2
170 : 190 1/10 V
HEX note 2 e 3
---
40091
cell discharge
Res. 1/10 Volt
Maximum cell voltage
2
230 : 270 1/10 V
HEX note 2 e 3
---
40092
Res. 1/10 Volt
40093
Duration of battery test
2
00 :99 min.
HEX note 2 e 3
---
40094
Battery test threshold
2
170 : 190 1/10 V
HEX note 2 e 3
---
40095
UPS power
2
Rotating
HEX note 1
---
40096
Nr. UPS connected
2
1 : 6
HEX
---
5.9.1
Notes on ‘Request for Programming Parameters’
Note
Measurements with rotating values
Rated input and output voltage
0x0
= 208 Volts
0x1
= 220 Volts
0x2
= 230 Volts
0x3
= 380 Volts
0x4
= 400 Volts
0x5
= 415 Volts
0x6
= 440 Volts
0x7
= 460 Volts
0x8
= 480 Volts
Rated frequency
0x0
= 50 Hz.
0x1
= 60 Hz.
Slew Rate
0x0
= 0.1 Hz./Sec.
0x1
= 0.5 Hz./Sec.
0x2
= 1.0 Hz./Sec.