8.2.3 Back-Up Time Of Standard Battery Module For Single UPS
In battery mode, the back-up time of a standard battery module (7AH/192V) upon full load is five minutes
approximately. Adding the number of battery modules can prolong the back-up time; see Table 8-3 for the back-up
time of different battery modules upon full load.
Table 8-18 Back-up time of standard battery module for single UPS
No. of the battery
module
Battery module
capacity
4800W 3800W 2800W 1800W 1300W 1000W
1 7.2AH
4.2m
6.7m
11.7m
25m
45.8m
1h7m
2
15AH
9.2m 13.3m 23.3m 50m 1h32m 2h13m
3
22AH
20m 28.3m 43.3m 1h26m 2h30m 4h1m
4 30AH
30m
38.3m
1h7m
2h5m
3h11m
5h16m
5
36AH
35m 43.3m 1h15m 2h20m 3h43m 5h55m
6
43AH
40m 55m 1h26m 2h45m 4h40m 6h21m
7
50AH
44m 58.3m 1h32m 3h4m 4h43m 6h40m
8
56AH
58m 83.3m 1h57m 3h16m 4h51m 7h05m
9
65AH
1h10m 1h32m 2h13m 3h45m 5h41m 8h11m
10
72AH
1h23m 1h57m 2h30m 4h18m 6h31m 9h27m
Note
The data in Table 8-3 is only for your reference, because the back-up time of batteries is affected by battery parameters, factories
and models, aging degree and other factors.
8.3 POD
UPS parallel POD is an option of the UPS. It provides safe and reliable power distribution function for the user. The
POD options are listed in Table 8-4.
Table 8-19 POD options
Model
Name
Dimension (Height × Width × Depth)
UF-POD112U11
1-in 1-out 1 + 1 parallel POD
430mm × 85mm × 625mm
UF-POD314U11
1-in 1-out 3 + 1 parallel POD
430mm × 170mm × 625mm
UF-POD314U31
3-in 1-out 1 + 1 parallel POD
430mm × 170mm × 625mm
UF-POD-0050
Output power distribution POD
430mm × 85mm × 80mm
8.3.1 1-In 1-Out 1 + 1 Parallel POD
The appearance of the 1-in 1-out 1 + 1 parallel POD is show in Figure 8-4.
Plastic panel
Figure 8-58 Appearance of 1-in 1-out 1 + 1 parallel POD
Remove the plastic panel to reveal the front panel of the 1-in 1-out 1 + 1 parallel POD, as shown in Figure 8-5.