94 Chapter 11 Specifications
NX UPS Single Module And Parallel System 250kVA ~ 800kVA User Manual
Chapter 11 Specifications
The chapter provides the UPS specifications.
11.1 Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in Table 11-1.
Table 11-1 European and international standards
Item
Normative reference
General safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS
EN62040-2/IEC62040-2/AS62040-2 (Class C3)
Method of specifying the performance and test requirements of UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529)
11.2 Environmental Characteristics
Table 11-2 Environmental characteristics
Rated power (kVA)
Item
Unit
250
300 E
300
400
500
600 E
600
800
Noise within 1m (in the front)
dB
70
79
76
Altitude m
≤
1000
Relative humidity
%RH
0 ~ 95, non condensing with corresponding temperature less than 40°C
Operating temperature
°C
0 ~ 40 (Note: Battery life is halved for every 10°C increase above 20°C)
Storage and transport
temperature for UPS
°C
- 40 ~ + 70
Over-voltage level
Over-voltage level 2
Pollution level
Pollution level 2
11.3 Mechanical Characteristics
Table 11-3 Mechanical characteristics
Rated power (kVA)
Item
Unit
250
300 E
300
400
500
600 E
600
800
Packing
excluded
mm
1200 × 900 × 1900
2400 × 900 × 1900
Dimensions
(W × D × H)
Packing
included
mm
1316 × 1046 × 2134
1316 × 1046 ×
2145*
Net
weight
800 800 850 900 1050 1050 1850 1950
Gross
weight
950 950 1000 1050 1200 1200 2000 2100
Color
Black
ZP7021
Protection degree, IEC
(60529)
IP20 (front door open or closed)
Note*: The 600kVA ~ 800kVA UPS system is 2400mm wide, packed in two wooded boxes 1316mm wide each