Operation
15
Current Record Window
Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions
that have been resolved. Use “page” (F1) and up / down arrow to read the events.
For a complete history log, refer to the Records tab of the Menu and Data Window.
Refer to
Table 13
for a complete list of supported status messages.
Battery
Battery voltage (V)
Battery bus voltage
Battery current (A)
Battery bus current
Battery temperature (°C)
Battery temperature °C
Remain Time Min.
Battery run time remaining
Battery boost charging
Battery is boost charging
Battery float charging
Battery is float charging
Battery disconnected
Battery is not connected
Records
(history log)
Displays all records in the history log
Language
(choices for text displayed) User may select any of 12 languages for LCD text.
Settings
Display contrast
Adjust the LCD display contrast
Date format set *
Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Date & time *
Set the date and time
Comm1 baud rate *
Communication baud rate setting for IntelliSlot 1
Comm2 baud rate *
Communication baud rate setting for IntelliSlot 2
Comm3 baud rate *
Communication baud rate setting for IntelliSlot 3
Communication address *
This setting is applicable to RS485 communication mode
Communication mode *
Communication Mode Setting
Callback times *
When IntelliSlot 1 Communication mode is Modem, this parameter sets
the number of times a number is redialed to send an alarm notification.
Phone No.1 *
When IntelliSlot 1 Communication mode is Modem, this is the first phone
number to be dialed (to send an alarm notification).
Phone No.2 *
When IntelliSlot 1 Communication mode is Modem, this is the second
phone number to be dialed (to send an alarm notification).
Phone No.3 *
When IntelliSlot 1 Communication mode is Modem, this is the third phone
number to be dialed (to send an alarm notification).
Command password *
User can modify the command password.
Command
(start/stop
battery &
system
tests)
Battery maintenance test * This test performs a partial discharge of the battery to obtain a rough
estimate of the battery capacity. Load must be between 20% and 100%.
Battery capacity test *
This test performs a full discharge of the battery to obtain a precise
measure of the battery capacity. Load must be between 20% and 100%.
System test *
This is a self-test of the UPS. When the user activates this function, a
popup window appears about 5 seconds later to show the results.
Stop testing *
Manually stops a battery maintenance test, battery capacity test or system
test.
Freshening Charge *
This command will allow a temporary Equalize charge for the batteries.
This charge is configurable for 1 to 36 hours
Stop Freshening Charge *
Manually stop a Freshening Charge
Modem Auto-answer
enable *
Manually enable the auto-answer function of modem.
Version
UPS version
Provides UPS firmware version numbers for the inverter, rectifier and
software display board.
UPS model
Provides UPS model information—for example, 400V-50Hz.
* Visible from the RMP, but the control is available at UPS only.
Table 12
Descriptions of RMP menus and data window items (continued)
Menu
Type
Item Type
Explanation