Installation Drawings
44
Figure 31 Cable connections
NOTES
1. All dimensions are millimeters.
2. Top and bottom cable entry available through removable access plates. Remove, punch to
accommodate conduit size and replace.
3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be
run in separate conduit.
4. Aluminum and copper-clad aluminum cables are not recommended,
5. All wiring is to be in accordance with national and local electrical codes.
Input/Output
Neutral
Bypass AC input cable
connections
AC output cable
connections
Input Neutral Bus
(side view)
Output Neutral Bus
(side view)
4.2 to external battery cabinet
Earth
Power Earth
(side view)
Battery connections (+ N -)
4.1 to battery