Specifications and Technical Data
62
15
F, P
480
21
30
24
30
208
42
60
15
F, P
600
17
30
19
20
208
42
60
15
F, P
208
49
60
54
60
208
42
60
15
F, P
220
46
60
51
60
208
42
60
15
F, P
240
42
60
47
50
208
42
60
10
F, P
480
14
20
16
20
208
28
40
10
F, P
600
12
15
13
15
208
28
40
10
F, P
208
33
40
36
40
208
28
40
10
F, P
220
31
40
34
40
208
28
40
10
F, P
240
29
40
32
40
208
28
40
Table 31
Multi-module bypass cabinet electrical data
System
Size
Type
kVA
System
I/P Voltage
(VAC)
System
Max Input
Current
System
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)
1+1
A00, BR0
30
208
104
125
208
83
125
20
208
70
90
208
56
70
15
208
53
70
208
42
60
10
208
35
45
208
28
40
CR1
30
208
107
150A
208
83
125
CR1, DR1
30
220
101
150A
208
83
125
CR1, DR1
30
480
46
70A
208
83
125
CR1, DR1
30
600
37
60A
208
83
125
CR1
20
208
71
100A
208
56
70
CR1, DR1
20
220
68
100A
208
56
70
CR1, DR1
20
480
31
50A
208
56
70
CR1, DR1
20
600
25
40A
208
56
70
CR1
15
208
54
80A
208
42
60
CR1, DR1
15
220
51
80A
208
42
60
CR1, DR1
15
480
23
40A
208
42
60
CR1, DR1
15
600
19
30A
208
42
60
CR1
10
208
36
60A
208
28
40
CR1, DR1
10
220
34
50A
208
28
40
CR1, DR1
10
480
16
30A
208
28
40
CR1, DR1
10
600
12
20A
208
28
40
Table 30
Maintenance bypass cabinet electrical data (dual input)
kVA Type
System
I/P Voltage
(VAC)
Rectifier
Max Input
Current
Rectifier
Input OCP
CB Size (A)
Bypass
Max Input
Current
Bypass
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)