60
User Manual 10H52188UM60 - Rev. 2 - 09/2012
Product Specifications
Liebert NXC
Chapter 9
Product Specifications
The chapter lists the UPS specifications.
9.1
Conformity and Standards
The UPS has been designed to conform to the European and international standards listed in Table 9-1.
Table 9-1 European and International Standards
Item Normative
reference
General and safety requirements for UPS
EN/IEC 62040-1
EMC requirements for UPS
EN/IEC 62040-2 (category C2)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/60950), electromagnetic emission and immunity (IEC/EN/61000 series) and construction (IEC/EN/60146 series and 60529)
9.2
Environmental Characteristics
Table 9-2 Environmental Characteristics
Item Unit
Rated power (kVA)
10 15
20
Noise within 1 m (from the front)
dBA
<58
<58
<58
Altitude
m
>2000, derating according to GB/T3859.2 when higher that 2000 m
Relative humidity
%RH
5 -95, non condensing
Operating temperature
°C
0 to 40; battery life is halved for every 10°C increase above 20°C
Storage and transport temperature for
UPS
°C
-20 to 70
Recommended battery storage
temperature
°C
-20 to 30 (20°C for optimum battery storage)
Overvoltage level
II
Pollution level
II
9.3
Mechanical Characteristics
Table 9-3 Mechanical Characteristics
Item Unit
Rated power (kVA)
10 15 20
Dimensions (W × D × H)
mm
500 x 860 x 1240
Net / Gross Weight
(excluding battery)
kg 115/145
Net / Gross Weight
(one string of battery)
kg 215/245
Net / Gross Weight
(two strings of battery)
kg 315/345
Net / Gross Weight
(three strings of battery)
kg 415/445
Net / Gross Weight
(four strings of battery)
kg 520/550
Color - Black
ZP-7021
Protection degree, IEC (60529)
-
IP20