Liebert NXL UPS
Operation and Maintenance Manual
250-300-400-800kVA
Page
59
3.3 Routine Maintenance
You should become thoroughly familiar with the equipment, but at no time should you go
beyond the specific procedures in this manual while performing maintenance or correcting
a malfunction.
If you have any doubt as to what must be done, call Liebert Services for further instructions
at the address shown in the beginning of this manual.
NOTE
Service and maintenance work must be performed only by properly trained and
qualified personnel and in accordance with applicable regulations as well as with
manufacturers’ specifications.
The UPS is designed for unattended operation, but does require some common-sense
maintenance.
•
Keep good records
— Troubleshooting is easier if you have historical background.
•
Keep it clean
— Maintain the UPS free of dust and any moisture.
•
Keep it cool
— Battery systems must be kept in the range of 22-26°C in order to
meet design specifications for capacity and longevity.
The UPS will reliably meet all performance specifications and design life at
temperatures up to 40°C (30°C for 800kVA UPS). However, performance and longevity
will be optimized when the UPS is operated at the same temperature as the batteries.
Contact Global Service Support for further details.
• Keep connections tight
— Tighten all connections at installation and at least
annually thereafter.
• Keep it inspected
— Periodically inspect external upstream switches and
downstream isolators to assure that the trip current settings are correct.
Become familiar with typical ambient conditions surrounding equipment so that
abnormal conditions may be more quickly recognized. Know what typical meter
readings are and where adjustable settings should be.
3.3.1
Record Log
Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered parameter indications including phase readings,
alarm messages, UPS mode of operation, air filter replacement date and observation notes.
A second log should be maintained for the battery module as directed by the battery
manufacturer.
A periodic walk-through inspection of the UPS and battery rooms is advised to check for
visible and audible indications of problems. Log the inspection, metered parameter
indications and any discrepancies.
3.3.2
Air Filters
The air filters must be inspected and serviced on a regular schedule. The period between
inspections will depend upon environmental conditions. Under normal conditions, the air
filters will require cleaning or replacement approximately every two months. Abnormal or
dusty conditions will require more-frequent cleaning and replacement of air filters. Inspect
installations in new buildings more often, then extend the inspection period as experience
dictates.
All NXL models have a replaceable air filter located inside the front doors. These filters can
be changed while the UPS is in operation.