Liebert NXL UPS
Operation and Maintenance Manual
250-300-400-800kVA
Page 68
Model Name
Nominal Power Rating at 0.9 PF Load
kVA
380V
400V
415V
Input Voltage to Rectifier
Vac
Rated Input Current (12P rectifier) @400V
A
Rated Inp Current (12 P + inp filter) @400V
A
Permissible Input Rectifier Voltage Range
Vac
291 (-23%) to 438 (+15%) 300 (-25%) to 460 (+15%)
310 (-25%) to 477 (+15%)
Input Voltage to Bypass
Vac
Bypass Input Current @400V- 110% LOAD
A
Permissible Bypass Input Voltage Range
Input Frequency
Hz
Permissible Input Frequency Range
Hz
%
%
%
-
-
-
Flexi Power Walk-In
sec
Battery Type
Number of battery cells
N°
Nominal Battery Bus
Vdc
Float Voltage
Vdc/Cell
End Of Discharge (EOD)
Vdc / Cell
Equalize Charge
Vdc/Cell
DC Ripple Voltage in float & Const V Ch.mode
%
Temperature Compensated Battery Charging
Inverter Type
Output Power
kW
Output Voltage
Vac
Output Voltage Regulation (loss&return of utility)
%
Output Voltage Regulation (100% Unbal. Load)
Output Frequency
Hz
Output Frequency Regulation
%
Output THDu at nominal voltage
%
Output THDu at nominal voltage Including a 100kVA
Non Linear Load per EN 62040-3
%
Capability to handle High Crest Factor Load
Capability to handle Step Load
%
Transient Recovery
msec
Capability to handle Leading PF Load
a) 0,5 lag to 0,9 lag
b) 0,9 lag to Nominal
c) at 0,95 Lead
d) at 0,9 Lead
e) at 0,8 Lead
Voltage Displacement
º
el
Inverter Overload rating, 3 phase
% FL
While specifying the parameters here, it is assumed that, extremes of all the conditions do not apply simultaneously.
380 / 400 / 415 (400V : default) 3-phase, 3-wires plus ground
800
Input THDi at nominal voltage at full load
Input Power Factor at nominal voltage
320 (-20%) to 460 (+15%)
1270
Optional
540 Vdc @ 380/ 400/ 415Vac
<1 (RMS value) < 3,4% Vpp
Selectable from 1.60 to 1.88 (for VRLA / Wet Cells)
2.30 (adjustable in 0.01 volt increments from 2.3-2.45 V/cell)
Liebert NXL
Liebert NXL UPS SPECIFICATIONS
Input Parameters
Battery & DC Parameters
1393
≥
0.80 with 12-Pulse
<3% with 12-pulse & Passive Active Filter
<10% with 12-pulse
<5% with 12-pulse & Passive Filter
≥
0.90 with 12-Pulse with Passive Filter
+/- 0.1
<2%
100 continuous
110 for 60 minutes
125 for 10 minutes
150 for 1 minute
20 (recovery to 95% of the voltage level)
2,5% (max)
e) Subject to 25% kW derate or 12,5% kW derate and 10°C ambient derate
3 : 1 (compliant with IEC 62040-3)
0-100 or 100-0
Up to 0.8 with the following ratings:
120deg +/- 1 deg
electrical (with 100% unbalanced load)
50 or 60
< % 2 (3-phase RMS average)
380 / 400 / 415 (400V : default) 3-phase, 4-wires plus ground
Output Parameters
IGBT-based Sine-Sine PWM Controlled
< % 1 (3-phase RMS average)
720
d) Subject to 12,5% kW derate or same Rating and 10°C ambient derate
a) Subject to Max. kVA rating
b) Subject to Max. kW rating
c) Subject to Max. kW rating
228 ~ 246 @ 380/ 400/ 415Vac
380 / 400 / 415 (400V : default) 3-phase, 4-wires plus ground
1238
2.15-2.3
45 to 66
50 or 60
≥
0.98 with 12-pulse & Passive Active Filter
VRLA (Valve Regulated Lead Acid) or Wet or NiCd
3 to 30 (selectable) in 1 sec. Increments
Table 5:
Specifications (800kVA UPS)