32 Chapter 5 Operator Control And Display Panel
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
Chapter 5
Operator Control And Display Panel
This chapter expands the functions and use of the components on the operator control and display panel of the UPS,
provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and
UPS alarm list, and tells how to select language and change the current data and time.
5.1 Introduction
The operator control and display panel is located on the front door of the UPS. It is the access point for operator
control and monitoring of all measured parameters, UPS and battery status and alarms. The operator control and
display panel is divided into three functional areas: mimic power flow chart, LCD display with menu keys, control keys,
as shown in Figure 5-1. The components on the operator control and display panel are described in Table 5-1.
LCD display with menu keys
EPO
INVERTER ON
INVERTER OFF
FAULT CLEAR
SILENCE ON / OFF
8
Control keys
1
2
4
5
3
6
7
Mimic power flow chart
STATUS
Lieber
t NX
20
08 -
1
0-
3
1
1
2 :
3
0 :
3
6
1
5
0
kV
A -3X3
单机
在线
正
常
?
旁路输入
主路输入
相电压
(V )
相电流
(A)
频率
(Hz )
线电压
(V )
功率因数
A( AB )
220
20 .5
50 .1
380
0.99
B( BC )
220
20 .5
50 .1
380
0 .99
C( CA )
220
20.5
50.1
380
0.99
主路空开闭合
01 - 12
手动开机
主路逆变供电
01 - 22
交流输出
单机在
线
NXr
15
0 kVA
1
6:
2
1:
1
7
交流输出
A(AB)
B(BC)
C(CA)
相电压
( V)
相电流
( A)
频率
(Hz)
线电压
( V)
功率因数
220
220
220
20.5
20.5
20.5
50.1
50.1
50.1
380
380
380
0.99
0.99
0.99
F1
F3
F4
F5
F2
Figure 5-1 Operator control and display panel
Table 5-1 Description of operator control and display panel
Part No.
Function
Key
Function
1 Rectifier
indicator
EPO EPO
switch
2
Battery indicator
INVERTER ON
Inverter start switch
3
Bypass indicator
INVERTER OFF
Inverter shutdown switch
4
Inverter indicator
FAULT CLEAR
Fault reset switch
5
Output indicator
SILENCE ON/OFF
Audible alarm silencing switch
6
Status indicator
F1 ~ F5
LCD menu keys
7 Buzzer
8
EPO switch cover
5.1.1 Indicators
The indicators mounted on the mimic power flow chart represent the various power paths and current UPS
operational status. The indicators are described in Table 5-2.
Table 5-2 Indicator description
Indicator State
Description
Rectifier indicator
Solid green
Rectifier in normal operation
Flashing green
Mains input normal, but rectifier not operating
Solid red
Rectifier fault
Off
Rectifier not operating, mains input abnormal