Chapter 5 Operator Control And Display Panel 39
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
Alarm Explanation
tolerance through the service configuration software
Inverter Asynchronous
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are
misaligned by more than six degrees in phase. The amplitude threshold is fixed for ±10% rating. This
alarm resets automatically once the condition is no longer true.
1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so, solve it first.
2. Verify the waveform of the bypass voltage
Inverter fault
Inverter output voltage outside specifications. Load transfers to bypass. The faulty power module will
shut down and open output relay, and the remaining power
modules will remain online
Fan fault
At least one of the cooling fans failed
Bypass STS Fail
At least one of the STSs at the bypass side is open or shorted. This fault is locked until power-off
Output Fuse Fail
At least one of the inverter output fuses is blown. The inverter shuts down, and the load transfers to
bypass if the remaining power modules are insufficient to support the load
Control power 1 fail
The UPS is operating but the redundant control power is abnormal or not available
Unit Over load
This alarm appears when the load arises above 105% of the nominal rating. The alarm automatically
resets once the overload condition is removed.
1. Find out if this alarm is true by checking which phase has overload through the load (%) displayed
on the LCD.
2. If this alarm is true, measure the actual output current to confirm if the displayed value is correct.
3. If yes, disconnect the non-critical load.
In a parallel system, this alarm will be triggered if the load is severely unbalanced
System Over load
This alarm appears when the total load rises above 105% of the nominal rating of the parallel
system.The alarm automatically resets once the overload condition is removed.
1. Find out if this alarm is true by checking which phase of which unit has overload through the load (%)
displayed on the LCD.
2. If this alarm is true, measure the actual output current to confirm if the displayed value is correct.
3. If yes, disconnect the non-critical load.
This alarm will be triggered if the load is severely unbalanced
Unit Over load Timeout
The UPS overload status continues and the overload times out.
Note that:
1. T
he highest loaded phase will indicate overload time-out first.
2. When the timer is active, then the alarm Unit Over load should also be active as the load is above
the nominal rating.
3. When the time has expired, the load transfers to static bypass. The inverter shuts down and will
restart after 10 seconds.
4. If the load decreases to lower than 95%, after five minutes, the system will transfer back to the
inverter.Check the load (%) displayed on the LCD to confirm if this alarm is true. If the LCD tells that
overload happens, then check the actual load and confirm if the UPS has overload before the alarm
happens
Byp. Abnormal Shutdown Both the bypass and inverter voltages are abnormal, and the output is off
Inverter Over Current
The inverter has overcurrent fault
Bypass Phase Reversed
The phase rotation of the bypass voltage is reverwed. Normally, phase B lags 120 degrees behind
phase A, and phase C lags 120 degrees behind phase B.
Check that the phase rotation of the UPS bypass supply is correct
Load Impact Transfer
A transfer to bypass occurred due to a large step load. The UPS can recover automatically. Turn on the
load equipment in stages to reduce the load impact on the inverter
Transfer Time-out
The load remains on bypass power owing to excessive number of transfers that occurred within the last
hour. The UPS can recover automatically and will transfer the load back to inverter power within an
hour
Load Sharing Fault
The UPSs in a parallel system are not sharing the load current correctly
DC Bus Abnormal
The DC bus voltage is abnormal and results in inverter shutdown. The load transfers to bypass
System Transfer
All UPSs in the parallel system transfer to bypass at the same time when one of them needs to transfer
to bypass. This message appears on the LCD of the UPS with passive transfer to bypass
DC Bus Over Voltage
The rectifier, inverter and battery converter shut down because the DC bus voltage is too high.. Check
if the rectifier has any fault. If no, check if an overload has occurred. Restart the inverter after the fault
is cleared
Bypass Over Current
The bypass current is above 135% of the rated current. The UPS alarms but has no action
LBS Active
The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus configuration
Mains Neutral Lost
The neutral line of the AC input mains is not detected
Battery ground fault
The battery ground fault option has detected a battery ground fault. Contact the local customer service
center of Emerson to inspect the battery installation