Additional Features for All Systems
7
Spike Suppression Module
The spike suppression module consists of AC filter
capacitors and dynamic peak limiting devices with a
response time of less than 1 nanosecond. Normal mode
high frequency noise is attenuated, while high-speed,
high-energy transients are limited to a safe level.
Transformerless System
(Not Available on Top Exit Units)
The Precision Power Center can be supplied without
a transformer for use with separate power condition-
ing systems. If step-down and isolation are not neces-
sary, transformerless systems provide the packaged
power system advantages of security, distribution,
monitoring, and upgrade flexibility.
Remote Emergency Power Off (REPO) Switch
Pressing the REPO push but-
ton activates the shunt trip
mechanism of the main input
circuit breaker, shutting down
the system.
The illuminated and fully
guarded REPO button is
mounted in a wall box. The
assembly includes 50 feet
(15.2m) of 3-conductor cable for
wiring to the unit. Additional
lengths of cable are available.
Floor Pedestals
In rooms without a raised
floor, the floor pedestals pro-
vide space for the bottom
entrance/exit of cables in Pre-
cision Power Center. The
height of the floor pedestals is
customer-specified. Standard
floor pedestal height range is
adjustable from 8.6 to 13.25 in. (218 to 336 mm).
Other available ranges: 6 to 8.5 in. (152 to 216 mm),
and 13.5 to 18 in. (343 to 457 mm). Non-raised floor
applications for the Precision Power Center are not
CSA approved.
Transient Suppression Plate
The transient suppression plate is a one-square-
meter plate mounted to (and bonded to) the high-
voltage junction box. It reduces the effects of tran-
sients on the ground system by providing a capaci-
tive coupling to building steel.
Phase Rotation Meter
The phase rotation meter is a hand-held instrument
with clip-on leads for connecting to the circuit under
test. The meter shows the circuit phase rotation in
“ABC” or “BAC” sequence.
The phase rotation meter can verify rotation
sequence of any circuit up to 600 volts.
Table 1
Features available by model
PPC
15-30 kVA
Top Exit
15-30 kVA
PPC
50-125 kVA
Top Exit
50-150 kVA
PPC
150-225 kVA
Panelboards
42 poles
standard
(one 42-pole
panelboard)
42 poles
standard
(one 42-pole
panelboard)
84 poles
standard
(two 42-pole
panelboards)
84 poles
standard
(two 42-pole
panelboards)
126 poles
standard
(three 42-pole
panelboards)
Flexible Output Cables and
Terminations
Available
Available
Available
Available
Available
Additional Pole Capacity
Optional 84
poles
Optional 84
poles
Optional 126 or
168 poles
Optional 126
poles
Optional 168 or
210 poles
Optional Panelboard Types
Optional
Optional
Optional
Optional
Optional
Subfeed Output Circuit
Breaker
Not available
Not available
Optional
(up to 225 A)
Not available
Optional
(up to 400 A)
High-Voltage Junction Box
with Flexible Input Cable
Standard
Not available
Standard
Not available
Standard
Low-Voltage Junction Box
with Flexible Input Cable
Optional
Not available
Optional
Not available
Optional
Secondary Class Surge
Arrester
Optional
Optional
Optional
Optional
Optional
Spike Suppression Module
Optional
Optional
Optional
Optional
Optional
Transformerless System
Optional
Not available
Optional
Not available
Optional
Remote Emergency Power
Off (REPO) Switch
Optional
Optional
Optional
Optional
Optional
K-20 Transformer
Optional
Optional
Optional
Optional
Optional
Multi-Winding Transformer
Optional
Optional
Optional
Optional
Optional
Floor Pedestals
Optional
Not available
Optional
Not available
Optional
Transient Suppression Plate
Optional
Not available
Optional
Not available
Optional