Specification for SiteLink-12
DESCRIPTION:
The SiteLink-12 is a 32-bit microprocessor-based communications device that provides
an interface for up to twelve Liebert Unit Controllers (IGM’s). The SiteLink-12 communicates to either the
SiteScan Monitoring System, or a third party software program utilizing a designated open standard
protocol (i.e. Modbus or BACnet). This device communicates to the SiteScan Monitoring System via a
twisted pair called the ARC156 network through an EIA-485 port at either 156K / 9600 or 38.4kbps baud.
It communicates to the third party software monitoring system via a 9-pin DTE male EIA-232 connector
(Portal Interface) or at the 5 pin EIA485 port communicating at either 9600bps or 38.4kbps baud. Twelve
EIA-422 ports are provided to connect Liebert Information Gathering Modules.
DIMENSIONS:
Module:
7 1/2" H x 11 1/4" W
19.05cm H x 28.58cm W
Enclosure:
12”H x 14.25" W x 2.85" D
(Painted steel)
419.1mm x 301.3mm x 78.6mm
See Enclosure Diagrams for mounting options.
POWER:
24VAC ± 10%, 50-60 Hz, 7.2VA power consumption.
(120/24VAC 40VA Transformer available)
ENVIRONMENTAL
OPERATING RANGE:
0
°
to 130
°
F (-17.8
°
to 54.4
°
C), 10 to 90% relative humidity, non-condensing
COMMUNICATION:
CMnet EIA-485 Port - Control Module network screw terminals
Switch selectable baud rates ARC156 / 9600 or 38.4bps
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2
Two (2) Portal Interface – One EIA-232, One EIA-485 2 / 4 wire (for Third Party
software selectable baud rate, 9600bps or 38.4kbps
One (1) Access port (for diagnostics)
Twelve (12) EIA-422 Ports (for Liebert unit connection) - screw terminal
MEMORY:
1024 kB Flash memory and 1024 kB non-volatile battery-backed RAM.
PROTECTION:
Voltage, current, and ESD protection on incoming power and ARC156 network
BATTERY:
Seven-year lithium battery provides a minimum or 10,000 hours or data
retention during power outages.
Liebert Corporation
Page 1 of 5 SL-27216 Rev. 4; 7/03