Configuring and operating the system
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
The operating topology of output relay 1 (Major) is normally closed (NC);
this means that the alarm contact is open (no alarm) when the relay is
energized, and closed (alarm condition), when not energized. Inversely, the
operating topology of output relays 2 to 8 is normally open (NO); this means
that the alarm contact is closed (alarm condition) when the relay is energized,
and open (no alarm), when not energized.
Clicking on
Output Alarm Relays
in the submenu screen for system settings
will display the following screen.
Screen 33
This screen displays the following information for output relays 1 to 8 on the
System Manager CIP:
•
the output relay number, and
•
the name of the alarm assigned to that input, or “Not in use!”, if no
alarm is assigned to that input.
To modify the alarm name for output relays 1 to 3 or to program or modify
the alarm name for output relays 4 to 8, click on the line for the applicable
output relay in the above screen; a screen similar to the following will be
displayed.