182
Maintenance
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Procedure 7.3 – Uploading the System Manager CIP configuration using
different software version
Step Action
1
Using the Ethernet port, connect the computer to the System Manager
CIP having the required settings to be uploaded to other System
Managers CIP with different software version.
2
Launch a browser (Internet Explorer or Netscape) and enter the IP
address of this System Manager CIP. The following screen should be
displayed if the passwords are enabled (Refer to section 5.6.5.31).
192.168. 0 . 1
3
Enter “admin” in the User Name field and the admin password.
Note:
Default password is “admin”. If the admin password has been
changed in the web interface, the new password shall be used.
The following screen should be displayed.
4
Write down all the settings under Settings menu.
Disconnect the System Manager CIP.
5
Using the Ethernet port, connect the computer to the System Manager
CIP to be set.
6
Repeat steps 2 and 3 using this System Manager CIP.
7
Modify the settings based on the settings retrieved in step 4.
–continued–