Parameter
Specifications
AP5C55BA (A7000507),
AP5C55BB (A7000509),
AP5C55BC (A7000510),
AP5C55CA (A7000508),
and AP5C55CB
(A7000511) shelves
15 A, 2-pole AC circuit breaker per
rectifier for 208/240 V supply (phase to
phase)
15 A, single-pole AC circuit breaker per
rectifier for 110/120 V supply (phase to
neutral)
AP5C55BE (A7000766)
shelf
20 A, 2-pole AC circuit breaker per
conduit for 208/240 V supply (phase to
phase)
20 A, single-pole AC circuit breaker per
conduit for 110/120 V supply (phase to
neutral)
AP5C55BG (A7000981)
shelf
40 A, 2-pole AC circuit breaker for
208/240 V supply (phase to phase)
40 A, single-pole AC circuit breaker for
110/120 V supply (phase to neutral)
AP5C55BH (A7001077)
shelf
20 A, 2-pole AC circuit breaker per
conduit for 208/240 V supply (phase to
phase)
20 A, single-pole AC circuit breaker per
conduit for 110/120 V supply (phase to
neutral)
Recommended
AC service input
AP5C55CC (A7000753)
shelf
30 A, 2-pole AC circuit breaker for
208/240 V supply (phase to phase)
30 A, single-pole AC circuit breaker for
110/120 V supply (phase to neutral)
Output voltage Nominal: –48.0 V dc
Range: –43.0 to –58.5 V dc
Factory setting: –52.1 V dc
Output power
Rectifier –48 V dc, 750 W: 750 W from 100 to 300 V ac, derated to
600 W at 85 V ac.
Rectifier –48 V dc, 1500 W: 1500 W from 200 to 300 V ac, derated
to 600 W at 85 V ac.
Input and output
protection
Internal fuses
Output over
voltage
protection
Hardware HVSD factory-set at 59.5 V dc
Software-adjustable HVSD, default at 59.5 V dc
Efficiency
Rectifier –48 V dc, 750 W:
89% at 100% load and 120 V ac
91.5% at 100% load and 240 V ac
>83%, from 40% to 100% load at a 120 V ac
>85%, from 40% to 100% load at a 240 V ac
Rectifier –48 V dc, 1500 W:
91.5% at 80% load and 240 V ac
>90%, from 40% to 100% load at a 240 V ac
–continued–