Configuring and operating the system
79
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Screen 12
This screen is used to set the nominal operational voltage (float) for the
system. This voltage is normally set according to the type of battery used with
the system. Note that in the above screen, if the
Present System Voltage
is
higher or lower than the
Nominal System Voltage
, it may be because the
Temperature Compensation
function is active.
If it is necessary to modify the setting (at initial start-up or when replacing the
battery by another type, for example), enter the new value (between –43.00
and –56.00) in the field above the
button, then click on the
button to confirm the new setting.
This screen also displays the following information:
•
a note to inform the user that the actual voltage may differ from the set
voltage when certain functions are active, and
•
a list of these functions and whether these are active or inactive.
5.6.5.2. Voltage Alarms
Clicking on
Voltage Alarms
in the submenu screen for system settings will
display the following screen.