Configuring and operating the system
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Screen 13
This screen is used to set the thresholds and hysteresis values for the system’s
High Voltage, Battery On Discharge and Low Voltage alarms. These are
normally set according to the type of battery used with the system.
Note:
Refer to section 5.6.5.20 for the setting of the System Manager CIP
High Voltage Shutdown (HVSD) threshold. The internal HVSD threshold
of the rectifiers is factory set at –56.5 V and is not field adjustable.