16
About this document
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CAUTION!
Optimizing the life of the equipment
Make sure there are no obstructions in front of the ventilation
openings of the system that could restrict the flow of air. A
minimum clearance of 1” (25 mm) is required in front and at
the rear of the equipment for proper airflow.
CAUTION!
Use the appropriate type of connecting lugs.
Do not use insulated No. 6 or No. 8 AWG “Ring” type lugs,
mainly those with a wider sleeve extending over the cable, as
these will cause congestion. Use regular non-insulated lugs
with clear shrinkable tubing.
Maximum tongue width is 0.625” (5/8”) for load clips,
0.4375” (7/16”) for main BR+ busbar and 0.31” (5/16”) for
10-position and 8-position BR+ busbar.
CAUTION!
Prevent damages to the controller.
Always remove the controller from the Lorain CIP and
Lorain CIP Access power shelf by pulling on it towards the
front, never upwards, as this may cause damages to the
controller and/or the connectors.
CAUTION!
Prevent loss of small parts.
Small parts, such as screws, washers, nuts, alarm fuses, load
clips covers, etc., may be loss if these fall into the slots at the
bottom of the shelf, in the rectifier section.
1.6. Reference
documents
In addition to the present document, it is recommended that the following
documentation be also available to perform the initial installation as well as
the operation and maintenance of an AP6C55CA/CB Lorain CIP or Lorain
CIP Access power system:
•
installation manual IM6C55C for the Lorain CIP and Lorain CIP Access
power system,
•
installation manual IM6C57E and user manual UM6C57E that refers to
the Ring & Distribution Module for the Lorain CIP Access power system,
•
other Emerson Network Power manuals as required, such as UM7C76BA
for the Temperature Probe Interface,
Summary of Contents for Lorain CIP 48120 AP6C55CA
Page 2: ......