172
Maintenance
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Step Action
13
In the GUI of the System Manager CIP, click on System Inventory and
check that the SW Revision corresponds to the new software version.
14
Modify and save settings as required.
–end–
Note:
Follow Procedure 7.2 and Procedure 7.3 if the settings from one
System Managers CIP have to be uploaded to other System Managers CIP.
7.4. Configuration
upload
The configuration upload is required when the settings propagation from one
System Manager CIP to another System Manager CIP is required. The
configuration upload is used in order to automatically set several System
Managers CIP with the same settings and avoid errors.
The settings can be downloaded from a System Manager CIP and saved on
the user’s computer in order to upload it to another System Manager CIP.
Various settings can be saved under different configuration files for the user’s
records. The upload cannot be done if the name of the configuration file is
different than “config.cil”. So make sure to rename the desired configuration
file “config.cil” before you upload it in the System Manager CIP. Otherwise,
it will not be recognized.
The download and upload operations can be done using any FTP software. In
this case, the WS_FTP Pro
®
has been used.
Procedure 7.2 is used when the System Managers CIP have the same software
version.
Procedure 7.3 is used when the System Managers CIP have different software
version.
To check the software version of a System Manager CIP, refer to section
5.6.3.3 System Inventory.
7.4.1.
System Manager CIP configuration upload using the same software version
Procedure 7.2 – Uploading the System Manager CIP configuration using the
same software version
Step Action
1
Connect the computer to the System Manager CIP from which the
download of the settings configuration is required through the Ethernet
port.
–continued–