184
Maintenance
UM6C55C (P7000597)
User Manual
Standard 10.00 (March 2008)
Lorain Power System (AP6C55CA/CB)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Step Action
11
Click Yes. The new System Manager CIP has now the required settings
that can be uploaded to other System Managers CIP having the same
software version.
12
To upload these settings, proceed with Procedure 7.2 starting at step 6.
–end–
7.5. Replacement of Lorain CIP and Lorain CIP Access components
The following subsections cover the procedures to be followed when
replacing various components in a Lorain CIP or Lorain CIP Access power
system.
Note:
The procedures in the following subsections involve work on a live
power system. Refer to the important
CAUTION
and
WARNING
boxes
in section
of this manual before starting these procedures
CAUTION!
Prevent damages caused by electrostatic
discharges (ESD).
This equipment includes solid-state devices sensitive to
electrostatic discharges (ESD). When performing
maintenance or repair procedures on a Lorain CIP or Lorain
CIP Access power system, it is therefore required to wear an
appropriate antistatic device (a bracelet for example) that is
properly connected to a designated antistatic grounding point
(on a framework, an anti-static floor mat or workbench mat,
etc.). ESD-protective packaging material shall also be used
when carrying/shipping ESD sensitive material.
7.5.1.
Replacing a CIP controller in a Lorain CIP power system
CAUTION!
Prevent damages to the controller.
Always remove the controller from the Lorain CIP power
shelf by pulling on it towards the front, never upwards, as this
may cause damages to the controller and/or the connectors.
Replace a Controller CIP as described in the following procedure.
Procedure 7.4 – Replacing a Controller CIP
Step Action
1
Notify the alarm center of the possibility of incoming alarms during this
procedure.
–continued–