3.2.3.1. Mechanical specifications of the Lorain CIP controllers
The mechanical specifications of the Lorain CIP controllers are listed in the
following table.
Table 3.4 – Mechanical specifications of the Lorain CIP controllers
Model Height
Width
Depth Weight
Controller CIP
0.83 kg (1.82 lb)
System Manager CIP
132 mm
(5.2 in.)
85.7 mm
(3.375 in.)
224.8 mm
(8.85 in.)
1.1 kg (2.4 lb)
3.2.3.2. Operating parameters of the Controller CIP and System Manager CIP
The operating parameters of the AP7C55BA Controller CIP are as follows:
Table 3.5 – Operating parameters of the AP7C55BA Controller CIP
Parameter
Specifications
Operating voltage
nominal:
–48 V dc
range:
–16 to –61 V dc
Operating temperature range
(see note below)
–40
°
C to 65
°
C (–40
°
F to 149
°
F), with excursions
to 75
°
C (167
°
F)
Output relay contacts
form C, 1 A capacity at 60 V dc
The operating parameters of the AP7C56BA System Manager CIP are as
follows:
Table 3.6 – Operating parameters of the AP7C56BA System Manager CIP
Parameter
Specifications
Operating voltage
nominal:
–48 V dc
range:
–16 to –61 V dc
Operating temperature range
(see note below)
–40
°
C to 65
°
C (–40
°
F to 149
°
F), with excursions
to 75
°
C (167
°
F)
Output relay contacts
form C, 1 A capacity
Note:
Although the Controller CIP, the System Manager CIP and the
rectifiers can operate on an individual basis at temperatures between 65
°
C
(149
°
F) and 75
°
C (167
°
F), and this for limited periods of time and/or
derating, 65
°
C (149
°
F) is the maximum operating temperature at the
system’s level.
Refer to Chapter 4 for the operational features of the Controller CIP and
System Manager CIP.
3.2.4.
Rectifier –48 V dc, 750 W and Rectifier –48 V dc, 1500 W
3.2.4.1. Mechanical specifications of the 750 W and 1500 W rectifiers
The mechanical specifications of the Rectifier –48 V dc, 750 W and the
Rectifier –48 V dc, 1500 W are listed in the following table.
Summary of Contents for Lorain CIP 48120 AP6C55CA