Table 5.3 – Low voltage disconnect settings (S2)
Low voltage
disconnect settings
S2-1 S2-2
S2-3
S2-4
S1-4
–40.0 V dc
Open
Open
Open
–42.0 V dc
Open
Open
Closed
–42.5 V dc
Open
Closed
Open
–43.0 V dc
Open
Closed
Closed
–43.5 V dc
Closed
Closed
Closed
–44.0 V dc
Closed
Open
Open
–44.5 V dc
Closed
Open
Closed
–45.0 V dc
Closed
Closed
Open
LVD1 contactor enabled
Closed
LVD1 contactor not enabled
Open
LVD2 contactor enabled
Closed
LVD2 contactor not enabled
Open
Note:
The settings in the shaded lines are the factory default settings.
5.3.4. Temperature
compensation
The Controller CIP has a temperature compensation function for adjusting the
float voltage of the rectifiers as a function of the temperature, in order to
optimize the charging of VRLA batteries and to prevent premature aging.
The temperature compensation slope can be adjusted by means of the S3 DIP
switch module. Refer to Figure 5.1, Table 5.1 and Table 5.4 for the switch
selection applicable to the desired temperature compensation slope.
Table 5.4 – Temperature compensation slope settings (S3)
Temperature compensation
slope voltage settings
S3-1 S3-2 S3-3
48 mV/
°
C
Open Open Closed
72 mV/
°
C
Closed
Closed
Closed
120 mV/
°
C
Open Closed Closed
144 mV/
°
C
Closed Open Closed
Temperature compensation OFF
x
x
Open
Note 1:
The reference temperature (T
ref
) is 20ºC.
Note 2:
The setting in the shaded line is the factory default setting
(providing the probe is installed).
Note 3:
The “x” means that the position of that switch does not matter.