Installation
Emerson
®
MPH2
™
User Manual
13
11. Slide the conduit into the conduit connector.
12. Tighten the conduit connector until it grips the conduit and crimps it securely.
Figure 2-2 Re-assembly to install an input power cable in conduit
Number
Description
Number
Description
1
Cover plate
5
Strain-relief collar w/Phillips-head screws
2
Terminal-block screws
6
Metal end plate (attached with 4 screws)
3
Terminal blocks
7
Conduit connector (field-supplied)
4
Terminal-block labels
8
Conduit (cable not shown)
Table 2-1
Hard-wired models—Connection terminal ratings
MPH2 Rating
≤
32 A
>32 A
Conductor Cross-Section Solid, Minimum
0.2 mm
²
0.5 mm
²
Conductor Cross-Section Solid, Maximum
6 mm
²
16 mm
²
Conductor Cross-Section Stranded, Minimum
0.2 mm
²
0.5mm
²
Conductor Cross-Section Stranded, Maximum
4 mm²
10 mm
²
Conductor Cross-Section, AWG/kcmil, Minimum
24
20
Conductor Cross-Section, AWG/kcmil, Maximum
10
6
Conductor Cross-Section Stranded, with Ferrule
without Plastic Sleeve, Minimum
0.25 mm
²
0.5 mm
²
Conductor Cross-Section Stranded, with Ferrule
without Plastic Sleeve, Maximum
4 mm
²
10 mm
²
Conductor Cross-Section Stranded, with Ferrule
with Plastic Sleeve, Minimum
0.25 mm
²
0.5 mm
²
Conductor Cross-Section Stranded, with Ferrule
with Plastic Sleeve, Maximum
4 mm
²
10 mm
²