Operations Manual
January 2017
FGD-MAN-0047
30
9.3
Troubleshooting guide
Table 9-1 Troubleshooting guide
Condition
Possible cause
Possible solution
Intermittent power
Faulty power supply or wiring.
Voltage is below operational voltage.
Failed electronic component(s).
Correct power supply or wiring.
Correct input voltage to unit.
Contact factory.
Unit not powering up
Faulty wiring or power supply.
Voltage is below operational voltage.
Blown inline fuse.
Water invasion of electronics.
Failed electronic component(s).
Correct wiring and power supply.
Correct input voltage to unit.
Replace inline fuse.
Contact factory.
Contact factory.
Unit powers up without display
Loose electronic boards.
Water invasion of electronics.
Failed electronic component(s).
Tightly fit electronic boards.
Contact factory.
Contact factory.
Sensor fault displays
Faulty power supply.
Faulty sensor.
Faulty sensor wiring.
Faulty junction box wiring.
Water invasion of electronics/junction box.
Failed electronic component(s).
Replace or correct power supply.
Replace sensor.
Correct sensor wiring at controller.
Correct junction box wiring.
Contact factory.
Contact factory.
Unstable 4-20 mA signal
Unshielded cables used for wiring.
Water invasion of electronics.
Failed electronic component(s)
Use shielded cables for wiring.
Contact factory.
Contact factory.
No 4-20 mA Output Signal
Current loop wiring is open.
Missing or incorrect placement of current output
jumper.
Current output is disabled by default for low powered
Millennium units.
Failed electronic component(s)
Close 4–20 mA signal loop.
Place current output jumper in correct position. See
Enable 4–20 mA signal under restricted menu option.
Contact factory.
Summary of Contents for Net Safety MLP-A-SC1100
Page 2: ......
Page 10: ......
Page 12: ...Operations Manual January 2017 FGD MAN 0047 2 ...
Page 22: ...Operations Manual January 2017 FGD MAN 0047 12 ...
Page 26: ...Operations Manual January 2017 FGD MAN 0047 16 ...
Page 28: ...Operations Manual January 2017 FGD MAN 0047 18 ...
Page 32: ...Operations Manual January 2017 FGD MAN 0047 22 ...
Page 38: ...Operations Manual January 2017 FGD MAN 0047 28 ...
Page 45: ...Operations Manual FGD MAN 0047 January 2017 35 ...
Page 47: ...Operations Manual FGD MAN 0047 January 2017 37 ...
Page 51: ...Operations Manual FGD MAN 0047 January 2017 41 ...
Page 53: ...Notes ...
Page 54: ...Notes ...
Page 55: ......