Operations Manual
FGD-MAN-0047
January 2017
29
Section 9:
Maintain
9.1
Periodic response check
We recommend the Millennium be verified or calibrated every
three months. A typical response check involves the application of
calibration gas to the sensor, then the observation of the response
LEDs, analog output, display, and external monitoring equipment. Be
sure to prevent unwanted response of external monitoring devices and
equipment during this procedure. If the Millennium response to
calibration gas is within its specified accuracy, then it is not necessary to
perform a calibration. For example, when 50% of full scale is applied,
the response is expected to be between 11.5 mA (47% of full scale) and
12.5 mA (53% of full scale). An additional consideration is the accuracy
and tolerance of the calibration gas which may be + or - a few percent. If
the calibration gas is + or - 10% of full scale, then the reading may be
from 10.7 mA (42% of full scale) to 13.3 mA (58% of full scale).
9.2
Troubleshoot
Response to the input should be checked and, if necessary, calibration
should be performed whenever any of the following occur. Refer to
for calibration instructions.
Excess negative drift is indicated by 2.5 mA current output.
Sensor or transmitter is connected or disconnected.
Long term or high concentration exposure to gas.
See
for assistance in troubleshooting. Also refer to
if returning equipment.
Repairs to Net Safety products should not be performed in the field.
Repairs to faulty or damaged equipment should only be performed at
the factory; otherwise warranty on the product will be voided.
Summary of Contents for Net Safety MLP-A-SC1100
Page 2: ......
Page 10: ......
Page 12: ...Operations Manual January 2017 FGD MAN 0047 2 ...
Page 22: ...Operations Manual January 2017 FGD MAN 0047 12 ...
Page 26: ...Operations Manual January 2017 FGD MAN 0047 16 ...
Page 28: ...Operations Manual January 2017 FGD MAN 0047 18 ...
Page 32: ...Operations Manual January 2017 FGD MAN 0047 22 ...
Page 38: ...Operations Manual January 2017 FGD MAN 0047 28 ...
Page 45: ...Operations Manual FGD MAN 0047 January 2017 35 ...
Page 47: ...Operations Manual FGD MAN 0047 January 2017 37 ...
Page 51: ...Operations Manual FGD MAN 0047 January 2017 41 ...
Page 53: ...Notes ...
Page 54: ...Notes ...
Page 55: ......