NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[34]
Programmable Relay Outputs
The EIB provides five (5) programmable alarm relays with dry Form-C contacts. Connect up to five (5) relay outputs to the IB2. Refer to
for pin-out information.
Refer to the ACU+ Instructions (UM1M820BNA or UM1M820DNA400) for programming information.
Relay Ratings: Refer to the following.
a.
1A Steady State @ 30V DC.
b.
3A Peak @ 30V DC.
The relays may be preprogrammed for specific functions. Refer to the configuration drawing (C-drawing) supplied with your system for
your system’s specific configuration.
Temperature Probes
Temperature probes can be connected to the optional EIB (ACU+ Extended Interface Board) mounted inside the distribution cabinet.
Refer to “Temperature Probes” on page 27.