NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[37]
Table 6.
Programmable Relay Outputs – EIB
Programmable Relay
Output
EIB
Pin No.
Alarms Assigned to this Relay
(Default)
Alarms Assigned to this Relay
(Custom)
9
NO
J8-5
The relays may be preprogrammed
for specific functions. Refer to the
configuration drawing (C-drawing)
supplied with your system for your
system’s specific configuration.
COM
J8-3
NC
J8-1
10
NO
J8-6
COM
J8-4
NC
J8-2
11
NO
J9-5
COM
J9-3
NC
J9-1
12
NO
J9-6
COM
J9-4
NC
J9-2
13
NO
J7-6
COM
J7-4
NC
J7-2
Note:
The relays energize during an alarm condition, closing the contacts between the C and NO terminals, and opening the
contacts between the C and NC terminals.